Terminal Assignment

signal
Description
1
24V-0
supply voltage (GND), internally connected with term. 31 and system GND (term. 19+37)
2
24V~
supply voltage (24V)
3,4
-
not used
5
BO1
Binary output 1. N.O. relay contact switching input power connected to terminal 8
6
BO2
Binary output 2. N.O. relay contact switching input power connected to terminal 8
7
BO3
Binary output 3. N.O. relay contact switching input power connected to terminal 8
8
IN1,2,3
Common relay contact for BO1, BO2, and BO3
9
IN4
Common relay contact for BO4
10
BO4
Binary output 4. N.O. relay contact switching input power connected to terminal 9
11
BO5
Binary output 5. N.O. relay contact switching input power connected to terminal 12
12
IN5
Common relay contact for BO5
13
IN6
Common relay contact for BO6
14
BO6
Binary output 6. N.O. relay contact switching input power connected to terminal 13
15
BO7
Binary output 7. N.O. relay contact switching input power connected to terminal 16
16
IN7
Common relay contact for BO7
17
IN8
Common relay contact for BO8
18
BO8
Binary output 8. N.O. relay contact switching input power connected to terminal 17
19
GND
Ground terminal (see NOTE below)
20
AO1
Analog output 1
21
AO2
Analog output 2
22
AO3
Analog output 3
23
AO4
Analog output 4
24
GND-1
ref. GND of RS485-1 (isolated)
25
485-1+
"+" signal for RS485-1 (isolated)
26
485-1-
"-" signal for RS485-1 (isolated)
27,28
not used
29
485-2+
"+" signal for RS485-2 (non-isolated)
30
485-2-
"-" signal for RS485-2 (non-isolated)
31
GND-2
ref. GND of RS485-2, int. connected with 24V-0 (term. 1) and system GND (term. 19+37)
32
-
not used
33
BI1
Binary input 1 (static dry contact) / pulse counter (fast totalizer)
34
BI2
Binary input 2 (static dry contact) / pulse counter (fast totalizer)
35
BI3
Binary input 3 (static dry contact) / pulse counter (fast totalizer)
36
BI4
Binary input 4 (static dry contact) / pulse counter (fast totalizer)
37
GND
Ground terminal (see NOTE below)
38
UI9
Universal input 9 (for NTC20kΩ / 0..10V / slow BI)
39
UI10
Universal input 10 (for NTC20kΩ / 0..10V / slow BI)
40
UI1
Universal input 1 (for NTC20kΩ / 0..10V / slow BI)
41
UI2
Universal input 2 (for NTC20kΩ / 0..10V / slow BI)
42
UI3
Universal input 3 (for NTC20kΩ / 0..10V / slow BI)
43
UI4
Universal input 4 (for NTC20kΩ / 0..10V / slow BI)
44
UI5
Universal input 5 (for NTC20kΩ / 0..10V / slow BI)
45
UI6
Universal input 6 (for NTC20kΩ / 0..10V / slow BI)
46
UI7
Universal input 7 (for NTC20kΩ / 0..10V / slow BI)
47
UI8
Universal input 8 (for NTC20kΩ / 0..10V / slow BI)
NOTE: All AOs, UIs, and BIs share the same ground potential. It is thus possible to connect just one combined GND signal for
all AOs, UIs, and BIs. Auxiliary terminals may be used if needed.
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
Table 8. Terminal assignment
11
X
X
X
X
X
X
-
-
-
-
X
-
-
X
-
-
X
-
-
X
-
X
X
-
X
X
-
-
X
-
-
X
-
X
X
-
X
X
-
X
X
-
X
X
-
-
X
-
-
X
-
X
X
-
X
X
-
X
X
-
-
X
-
-
X
-
X
X
X
X
X
X
X
X
X
-
-
-
X
X
X
X
X
X
X
X
X
-
-
-
X
X
-
X
X
-
X
X
-
X
X
-
X
X
-
-
X
-
-
X
-
X
X
-
X
X
-
X
X
-
X
X
-
-
X
-
-
X
-
-
X
-
-
X
-
EN1Z-0970GE51 R1112

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents