Clea2026Bxx Connection Examples - Honeywell Centra Line EAGLE Installation & Commissioning Instructions

Table of Contents

Advertisement

CLEA2026Bxx Connection Examples

TOTALIZER
1: GND
2: SIGNAL
1
24 25 26
~
1
2
24Vac
!
WARNING
Risk of electric shock or equipment damage!
Low voltage and line voltage must not be wired
within the same block.
For fusing specifications see section "Fusing Specifications" on page 10.
NOTE: Use a min. distance of 10 cm between power cables and 0...10 V / sensor cables in order to prevent signal
disturbances on the 0...10 V / sensor cables.
EAGLE CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
DRY
CONTACT
1: GND
2: SIGNAL
2
1
2
27 28 29 30 31 32
BLOCK 1
5
6
7
8
FAN
1: 24V~
2: GND
Fig. 22. CLEA2026Bxx connection example
NTC20kOHM
NTC20kOHM
SENSOR
SENSOR
1: GND
1: GND
2: SIGNAL
2: SIGNAL
1
2
33 34 35 36
37
38 39
CLEA2026Bxx
BLOCK 2
9 10
11 12 13 14 15 16 17 18
L
N
FAN
1
2
1: 220V N
FAN
2:
220V~
1: 24V 0
~
M
2: 24V
~
13
ACTIVE SENSOR
1: GND (24V 0)
~
2: 24V POWER
~
3: 0...10 VDC
1
2
40 41 42 43 44 45 46 47
19
20
21
1
2
FAN
1: 24V 0
~
M
2: 24V
~
24V
~ DRIVE with
0...10V SIGNAL
1: GND (24V 0)
~
2: 24V POWER
~
3: 0...10 VDC
EN1Z-0970GE51 R1112
1
2
3
1
2
22
23
1
2
1
2
3
M
0...10 VDC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents