4.13 Submenu Alarm
Entry from table
The functions incorporated in this menu can be selected using
the STEP and DATA keys after ENTER is pressed.

Error Register

MAX-Alarm
MIN-Alarm
Submenu
Alarm
4.13.1 Error Register
All detected errors (Error 0 to 9, A to C) are stored in this
register. All detected errors will remained stored until the
register is manually reset (using the ENTER key).
In the example, Error 0 (Empty Pipe) and Error 3 (Flowrate >
130 %) have been registered since the last reset.
Error Register
0...3...
The following display appears after pressing ENTER:
Reset: ENTER
Help Text: STEP
After pressing ENTER the error register is cleared.
Error Register
...........
(4.13.1)
(4.13.2)
(4.13.3)
Electromagnetic Flowmeter
Press the STEP key to access the help text which displays a
clear text description for each error code.
.0.
Empty Pipe
Error 0 = Empty pipe
.8.
Urefn too large
Error 8 = negative reference voltage too large
Exit the help text information by pressing C/CE.

4.13.2 Setting the MAX-Alarm

MAX-Alarm
130 %
The limits for the desired MAX-Alarm value can be set in 1 %
steps from 0 % to 130 %. This value applies to both the forward
and reverse flow directions.
When MAX-Alarm is selected the contact is actuated when the
flowrate exceeds the limit value set. If this occurs, an upward
pointing blinking arrow is displayed.
F
F
MAX-Alarm limit value = 110 %
For flowrates >110 % a upward pointing blinking arrow is
displayed next to the flow direction indicator in the 1st line. If the
MAX-Alarm value is set to 0 %, the option is turned off and no
alarm arrow is displayed when the flowrate exceeds the value.
COPA-XE / MAG-XE
(set)
115.67 %
6789.12 l
25