4.10 Density
Numeric entry
When the flowrate indication and the totalization are to be in
mass units, g, kg, t pounds or uton, a fixed density value can be
entered for the calculations.The conversion to mass flowrate
can be set in the range from 0.01 to 5.00000 g/cm
Density
2.54300
4.11 System Zero
Numeric entries
After the installation has been completed the zero should be ad-
justed at the converter. The flowrate is to be reduced to zero.
The adjustment can be made automatically by the converter. A
manual entry is also possible. The zero value is set to 0 Hz
when the C/CE key is pressed. A measured output frequency
value can then be entered as the correction value.
Select the parameter "System Zero" and press ENTER.
For security the following message is displayed:
System Zero
3.5 Hz
The choice between "manual" and "automatic" can be made
using the STEP or DATA keys.
The converter initiates the automatic adjustment procedure
when ENTER is pressed. The values in the display count down
from 255 to 0. The adjustment procedure is repeated 4 times.
The final zero value must be within the limits set in the converter
of ± 50 Hz. If the value is outside of the limits the zero
adjustment is not completed. The value determined by the
converter is displayed in the 2nd line.

4.12 Submenu Units

The following parameters are included in this submenu:
Engineering Units Q
max
Engineering Units Q
max
Engineering units with Units Factor, user programmable
Unit Name, user programmable and
Prog. Units with/without density correction.
The last three entry parameters are required for any new user
units which are not included in the program or in the table in
Sect. 4.12.1. When this function is utilized the factory set unit
"kgal" is cleared.
Submenu
Units
3
.
g/m3
Electromagnetic Flowmeter
4.12.1 Units Qmax
Entry from table
The units listed in the following table can be selected using the
STEP and DATA keys and accepted by pressing ENTER.
Units
l/s
Units
Liter
Hectoliter
Cubic meter
Imperial gallon
U.S. million gallons per day
U.S. gallon
Barrels, Brewery
Barrels, Petrochemical
Kilogram
Ton
Gram
Milliliter
Megaliter
Pound (454 g)
US-Ton
The units selected apply to Q
flowrate values in the display when they are displayed in direct reading
engineering units.
COPA-XE / MAG-XE
Q
max
l/s
l/min
l/h
hl/s
hl/min
hl/h
3
m
/s
3
m
/min
3
m
/h
3
m
/d
ipgs
igpm
igph
igpd
mgd
gpm
gph
bbl/s
bbl/min
bbl/h
bls/day
bls/min
bls/h
bbl/d
kg/s
kg/min
kg/h
kg/d
t/s
t/min
t/h
t/d
g/s
g/min
g/h
ml/s
ml/min
ml/h
Ml/min
Ml/h
Ml/day
lbs/s
lbs/min
lbs/h
uton/min
uton/h
Uton/day
, Qmax and to the instantaneous
maxDN
23

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mag-xe

Table of Contents