4.20.1 Display 1st Line
Entry from table
After pressing ENTER the display mode for the instantaneous
flowrate can be selected using the STEP or DATA keys.
1st Display Line
Q [%]
Display Selections:
Q [%]
Flowrate in %
Q [Units]
Flowrate in engineering units
Bargraph
Flowrate in a bargraph presentation
Totalizer
Totalized flow value for forward and
reverse flow directions or forward only
4.20.2 Display 2nd Line
Entry from table
The values displayed in the 2nd line can also be individually
configured. See 1st display line for selections.
4.20.3 Multiplex 1st Display Line
Entry from table
1st Line Multipl.
off
After pressing ENTER the STEP/DATA keys can be used to
select an additional value to be displayed in the 1st line in a
multiplex mode. The values alternate automatically in a
10 second cycle.
Multiplex Display Selections
Q [%]
Flowrate in %
Q [Units]
Flowrate in engineering units
Bargraph
Flowrate in a bargraph presentation
Totalizer
Totalized flow value for forward and
reverse flow directions or forward only
Off
No multiplex display values
Electromagnetic Flowmeter
4.20.4 Multiplex 2nd Display Line
Entry from table
The 2nd display line can also operate in the multiplex mode.
For display selections see Multiplex 1st Display Line.
2nd Line Multipl.
TAG Number
4.21 Submenu Operating Mode
Entry from table
The STEP or DATA keys can be used to select one of two
available operating modes, Standard/Fast, as well as the flow
direction and the flow direction indication.
4.21.1 Operating Modes Standard/Fast
Entry from table
The operating mode "Standard" is used for continuous flow
metering.
The operating mode "Fast" is used for short time batch
operations > 3 s and for piston pump operation when the
converter incorporates a higher excitation frequency capability.
In this operating mode the improved reproducibility for short
time batch and piston pump applications is achieved by
accelerated signal measurements.
Press ENTER to accept the selection.
Operating Mode
Standard
4.21.2 Flow Direction (Forward and Reverse)
Entry from table
After pressing ENTER the STEP or DATA keys can be used to
select forward and reverse metering or forward metering only.
If forward is selected, then the flowmeter measures only when
the flow is in the forward direction. The totalizer values are the
integrated flow are for this direction. The reverse flow is not
measured or totalized. There are no reverse pulses available
on terminals V8, V9, or Ux/V8.
Flow Direction
Forward/Reverse
COPA-XE / MAG-XE
33