Disconnect Switch Sizing (Dss); Low Voltage Wiring; Control Power Transformer; Field Installed Ac Control Wiring - Trane Voyager Commercial Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners with reliatel controls and estage 27.5 to 50 tons - 60 hz, 22.9 to 41.7 tons 81-148 kw - 50 hz
Hide thumbs Also See for Voyager Commercial:
Table of Contents

Advertisement

I I n n s s t t a a l l l l a a t t i i o o n n E E l l e e c c t t r r i i c c a a l l
MOP = (2.25 x Load 1) + Load 2 + Load 3 + Load 4
N N o o t t e e : : The MOP value stamped on the nameplate is
the largest of the two calculated values.
RDE = (1.5 x Load 1) + Load 2 + Load 3 + Load 4
N N o o t t e e : : Select an over current protection device equal to
the MOP value. If the calculated MOP value does
not equal a standard size protection device listed
in NEC 240-6, select the next lower over current
protection device. If the calculated MOP value is
less than the MCA value, select the lowest over
current protection device which is equal to or
larger than the MCA, providing the selected over
current device does not exceed 800 amps.
N N o o t t e e : : Select a Dual Element Fuse equal to the RDE
value. If the calculated RDE value does not equal
a standard dual element fuse size listed in NEC
240-6, select the next higher fuse size. If the
calculated RDE value is greater than the MOP
value, select a Dual Element fuse equal to the
calculated MOP (Maximum Over current
Protection) value.

Disconnect Switch Sizing (DSS)

Calculation A — YC*, TC*, and TE* units:
DSS = 1.15 X (LOAD1 + LOAD2 + LOAD4)
N N o o t t e e : : For TE* units, use calculations A and B.
Calculation B — TE* units:
DSS = 1.15 X (LOAD3 + Supply Fan FLA +
Exhaust Fan FLA).
N N o o t t e e : : Use the larger value of calculations A or B to size
the electrical disconnect switch.

Low Voltage Wiring

An overall layout of the various control options
available for a Constant Volume application is
illustrated in
, p.
33.
Figure 22, p. 35
various control options for a Variable Air Volume
application. The required number of conductors for
each control device are listed in the illustration.
A typical field connection diagram for the sensors and
other options are shown in the following section
"Remote Panels and Sensors". These diagrams are
representative of standard applications and are
provided for general reference only. Always refer to the
wiring diagram that shipped with the unit for specific
electrical schematic and connection information.
N N o o t t e e : : All field wiring must conform to NEC guidelines
as well as state and local codes.
32
illustrates the

Control Power Transformer

W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . V V e e r r i i f f y y t t h h a a t t n n o o
p p o o w w e e r r i i s s p p r r e e s s e e n n t t w w i i t t h h a a v v o o l l t t m m e e t t e e r r . .
The 24 volt control power transformers are equipped
with internal circuit breakers. They are to be used only
with the accessories called out in this manual. If a
circuit breaker trips, be sure to turn off all power to the
unit before attempting to reset it.
On units equipped with the VFD option, an additional
control power transformer is used. The secondary is
protected with fuses. Should the fuse blow, be sure to
turn off all power to the unit before attempting to
replace it.

Field Installed AC Control Wiring

W W A A R R N N I I N N G G
H H a a z z a a r r d d o o u u s s V V o o l l t t a a g g e e ! !
F F a a i i l l u u r r e e t t o o d d i i s s c c o o n n n n e e c c t t p p o o w w e e r r b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g c c o o u u l l d d
r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r s s e e r r i i o o u u s s i i n n j j u u r r y y . .
D D i i s s c c o o n n n n e e c c t t a a l l l l e e l l e e c c t t r r i i c c p p o o w w e e r r , , i i n n c c l l u u d d i i n n g g r r e e m m o o t t e e
d d i i s s c c o o n n n n e e c c t t s s b b e e f f o o r r e e s s e e r r v v i i c c i i n n g g . . F F o o l l l l o o w w p p r r o o p p e e r r
l l o o c c k k o o u u t t / / t t a a g g o o u u t t p p r r o o c c e e d d u u r r e e s s t t o o e e n n s s u u r r e e t t h h e e p p o o w w e e r r
c c a a n n n n o o t t b b e e i i n n a a d d v v e e r r t t e e n n t t l l y y e e n n e e r r g g i i z z e e d d . . V V e e r r i i f f y y t t h h a a t t n n o o
p p o o w w e e r r i i s s p p r r e e s s e e n n t t w w i i t t h h a a v v o o l l t t m m e e t t e e r r . .
W W A A R R N N I I N N G G
P P r r o o p p e e r r F F i i e e l l d d W W i i r r i i n n g g a a n n d d G G r r o o u u n n d d i i n n g g
R R e e q q u u i i r r e e d d ! !
F F a a i i l l u u r r e e t t o o f f o o l l l l o o w w c c o o d d e e c c o o u u l l d d r r e e s s u u l l t t i i n n d d e e a a t t h h o o r r
s s e e r r i i o o u u s s i i n n j j u u r r y y . .
A A l l l l f f i i e e l l d d w w i i r r i i n n g g M M U U S S T T b b e e p p e e r r f f o o r r m m e e d d b b y y q q u u a a l l i i f f i i e e d d
p p e e r r s s o o n n n n e e l l . . I I m m p p r r o o p p e e r r l l y y i i n n s s t t a a l l l l e e d d a a n n d d g g r r o o u u n n d d e e d d
f f i i e e l l d d w w i i r r i i n n g g p p o o s s e e s s F F I I R R E E a a n n d d E E L L E E C C T T R R O O C C U U T T I I O O N N
h h a a z z a a r r d d s s . . T T o o a a v v o o i i d d t t h h e e s s e e h h a a z z a a r r d d s s , , y y o o u u M M U U S S T T f f o o l l l l o o w w
r r e e q q u u i i r r e e m m e e n n t t s s f f o o r r f f i i e e l l d d w w i i r r i i n n g g i i n n s s t t a a l l l l a a t t i i o o n n a a n n d d
g g r r o o u u n n d d i i n n g g a a s s d d e e s s c c r r i i b b e e d d i i n n N N E E C C a a n n d d y y o o u u r r l l o o c c a a l l / /
s s t t a a t t e e / / n n a a t t i i o o n n a a l l e e l l e e c c t t r r i i c c a a l l c c o o d d e e s s . .
N N O O T T I I C C E E
U U s s e e C C o o p p p p e e r r C C o o n n d d u u c c t t o o r r s s O O n n l l y y ! !
F F a a i i l l u u r r e e t t o o u u s s e e c c o o p p p p e e r r c c o o n n d d u u c c t t o o r r s s c c o o u u l l d d r r e e s s u u l l t t i i n n
e e q q u u i i p p m m e e n n t t d d a a m m a a g g e e a a s s t t h h e e e e q q u u i i p p m m e e n n t t w w a a s s n n o o t t
d d e e s s i i g g n n e e d d o o r r q q u u a a l l i i f f i i e e d d t t o o a a c c c c e e p p t t o o t t h h e e r r t t y y p p e e s s o o f f
c c o o n n d d u u c c t t o o r r s s . .
RT-SVX34R-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents