Trane Voyager Commercial Installation, Operation And Maintenance Manual page 20

Packaged rooftop air conditioners with reliatel controls and estage 27.5 to 50 tons - 60 hz, 22.9 to 41.7 tons 81-148 kw - 50 hz
Hide thumbs Also See for Voyager Commercial:
Table of Contents

Advertisement

U U n n i i t t D D i i m m e e n n s s i i o o n n s s a a n n d d W W e e i i g g h h t t s s
Figure 14. Center of gravity
Z (see note 2)
Table 4. Approximate units operating weights — lbs./kg
Basic Unit Weights
Unit
Model
YC Low
YC High
(60Hz/
Heat
Heat
50Hz)
330/275 3720 / 1687
4150 / 1882
360/305 3795 / 1721
4225 / 1916
420/350 3876 / 1758
4306 / 1953
480/400 4825 / 2189
4950 / 2245
600/500 5077 / 2303
5202 / 2360
Note: Weights shown represent approximate operating weights and
have a ±10% accuracy. To calculate weight for a specific unit
configuration, utilize TOPSS™ or contact the local Trane® sales
representative. ACTUAL WEIGHTS ARE STAMPED ON THE UNIT
NAMEPLATE.
Table 5. Point loading average weight— lbs./kg
Unit
Model
A
B
(60Hz/
50Hz)
852 /
695 /
330/275
386
315
878 /
681 /
360/305
398
309
841 /
842 /
420/350
381
382
835 /
869 /
480/400
378
394
882 /
931 /
600/500
400
422
Notes:
1.
Point loading is identified with corner A being the corner
with the compressors. As you move clockwise around the
unit as viewed from the top, mid-point B, corner C, corner
D, mid-point E and corner F.
2.
Point load calculations provided are based on the unit
weight for YC high heat gas models.
20
Y
X
TC
TE
3590 / 1628 3610 / 1637.5
3665 / 1662 3685 / 1671.5
3746 / 1699
3766 / 1708
4565 / 2071 4600 / 2086.5
4827 /
4852 / 2201
2189.5
C
D
E
F
754 /
740 /
602 /
504 /
342
335
273
228
750 /
713 /
577 /
622 /
340
323
262
282
669 /
735 /
582 /
634 /
303
333
264
287
950 /
748 /
769 /
776 /
431
339
349
352
954 /
740 /
844 /
847 /
433
336
382
384
RT-SVX34R-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents