Samsung AM FN1DEH Series Installation Manual page 16

Hide thumbs Also See for AM FN1DEH Series:
Table of Contents

Advertisement

Performing Leak Test & Insulation (Continued)
Insulation
Gas pipe
10mm
10mm
Gas pipe
16
5
Select the insulation of the refrigerant pipe.
 Insulate the gas side and liquid side pipe referring to the thickness
 Indoor temperature of 30°C and humidity of 85% is the standard condition.
 Insulator's heat-resistance temperature should be more than 120°C.
<Geological condition>
- High humidity places such as shoreline, hot spring, near lake or river, and
<Operation purpose condition>
- Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
- The ceiling frequently exposed to moisture and cooling is not covered.
- The place where the pipe is installed is highly humid due to the lack of
Refrigerant pipe before EEV kit and MCU or without EEV kit and MCU
 You can contact the gas side and liquid side pipes but the pipes
Insulation
Liquid pipe
Refrigerant pipe after EEV kit and MCU
10mm
10mm
Install the insulation not to get wider and use the adhesives
on the connection part of it to prevent moisture from entering.
Liquid pipe
Wind the refrigerant pipe with insulation tape if it is exposed to
outside sunlight.
Install the refrigerant pipe respecting that the insulation does not
get thinner on the bent part or hanger of pipe.
Add the additional insulation if the insulation plate gets thinner.
Additional insulation
according to the pipe size.
If installing in a high humidity condition, use one grade thicker insulator by
referring to the table below.
If installing in an unfavorable conditions, use thicker one.
Insulation Type (Heating/Cooling)
Standard
Pipe
Pipe size
[30°C, 85%]
Ø6.35 ~ Ø9.52
Liquid
pipe
Ø12.7 ~ Ø50.80
Ø6.35
Ø9.52~Ø25.40
Gas
pipe
Ø28.58~Ø44.45
Ø50.80
When installing insulation in places and conditions below, use the same insulation
that is used for high humidity conditions.
ridge (when the part of the building is covered by earth and sand.)
e.g. The pipe installed at a corridor of a dormitory and studio or near an
exit that opens and closes frequently.
ventilation system.
should not be pressed.
When contacting the gas side and gas side pipe, use 1 grade thicker
insulator.
Install the gas side and liquid side pipes, leave 10mm of space.
When contacting the gas side and liquid side pipe, use 1 grade
thicker insulator.
Hanger
a×3
a
High humidity
[30°C, over 85%]
EPDM, NBR
9t
13t
13t
19t
Internal temperature
is higher than 120°C
25t
19t
32t
25t
38t
Refrigerant pipe insulation
Remarks