Application Examples; Safety Function For Units With Cross Fault Detection (Pay Attention To "Unit Programming"!); Safety Function For Units Without Cross Fault Detection (Pay Attention To "Unit Programming"!) - DOLD SAFEMASTER UF 6925 Translation Of The Original Instructions

Emergency stop module
Table of Contents

Advertisement

Available languages

Available languages

Application Examples

DC24V
on
K3
K4
A1+
S33
S34
S21
A2
0V
A jumper must be fitted S33 - S34 for the automatic On function. The On pushbutton is not required. The required start function has to be selected on
switch S1 before starting the device. (see "Unit Programming").
Functioning of the external contactors is monitored by looping the NC contacts into the closing circuit (terminals S33 - S34).

Safety function for units with cross fault detection (pay attention to "Unit Programming"!)

emergency
stop
S21
S22
S11
Fct.: E-stop
SIL 3, PL e, Cat. 4

Safety function for units without cross fault detection (pay attention to "Unit Programming"!)

emergency
stop
S21
S22
S11
Fct.: E-stop
SIL 3, PL e, Cat. 4
1)
1)
To achieve the safety classifications a crossfault safe wiring has to be installed.
safety function
S22
S11
S12
13
23
33
UF6925
14
24
34
K3
K4
M11695
S12
M10768
Fct.: Safety gate
SIL 3, PL e, Kat. 4
S12
M10772
Fkt.: Safety gate
SIL 3, PL e, Cat. 4
Sliding door
is closed
S21
S22
S11
S12
M10778
Sliding door
is closed
S21
S22
S11
S12
M10770
1)
19
UF 6925 / 30.08.17 en / 895