Download Print this page

Siemens 2KG13 Information On Safety And Commissioning page 7

Angular geared motors

Advertisement

Available languages

Available languages

Air clearances between bare live parts themselves and be-
tween bare live parts and earth must be ≥ 5.5 mm
(U
≤ 690 V).
rated
It must be ensured that the terminal box does not contain any
foreign bodies, dirt or moisture. Seal any unused cable entry
openings to protect against any dust and water.
Secure the key for test operation without drive components if
applicable. For motors with brakes, check that the brakes are
operating perfectly before commissioning.
To change the direction of rotation of the motor, two of the
three phase conductors must be interchanged.
6
Operation
Vibration levels of v
≤ 3.5 mm/s (P
rms
mm/s (P
> 15 kW) are quite acceptable.
N
If deviations from normal operation occur – e.g. increased
temperatures, noises, vibration, leakage of oil, the geared
motor should be switched off in the event of any uncertain-
ties. Determine the causes and contact the manufacturer, if
necessary. Do not disconnect protective equipment, even un-
der test operation.
In the case of motors with separate fan, the separately-
driven fan must be switched on throughout motor operation.
Interval
Part
Every 10 000 ope-
Gearbox
rating hours or
after 4 years
Every 3 000
Torque
operating hours
bracket
In the case of dirty
Motor
operation conditions,
at least every
10 000 operating hours
According to
Brake
operating conditions,
at least every
3 000 operating hours
7
Further information
Information provided about any additional equipment must be
observed! Additional information is available in our detailed
operating and maintenance instructions (German / English /
French). They will be sent to you on request if the gearbox ty-
pe and serial number (SNR) are also specified.
These notes on safety and commissioning must be kept
for future reference!
______________________________________________________________________________________
Siemens
04.2003
≤ 15 kW) or v
≤ 4.5
N
rms
Maintenance
Oil change (under extreme operating con-
ditions, such as increased ambient tempe-
ratures or extreme temperature fluctu-
ations, the oil change must be carried out
sooner).
Check for play in direction in which force
is applied.
Inspect the motor and clean cooling air
channels. Open and close condensated
water holes from time to time.
Check brake of motors with fitted brake.
If necessary, replace worn parts and adjust
the air gap.
Bestell-Nr./Order No. 2KG1900-3AA00-0AA0
Deutsch / English / Français
7/15

Advertisement

loading