Electrical - Vent-Axia HR100R Installation And Servicing Instructions

Mini air handling unit

Advertisement

Continuous Normal Speed
HR100R Terminals
Black
L
1
Brown
L
2
Blue
N
Green/Yellow
Continuous Boost Speed
HR100R Terminals
Black
L
1
Brown
L
2
Blue
N
Green/Yellow
VCON100: Manual Normal to Boost Speed
Switching and ON/OFF Control
HR100R Terminals
Black
L
1
Brown
L
2
Blue
N
Green/Yellow
NBSW and PCSW: Manual Normal to Boost
Speed Control
HR100R Terminals
L
1
L
2
N
HS6: Automatic Normal to Boost Speed Control
HR100R Terminals
Black
L
1
Brown
L
2
Blue
N
Green/Yellow
10
3 amp fused supply
Live
Neutral
Earth
3 amp fused supply
Live
Neutral
Earth
3 amp fused supply
L
Live
N
Neutral
Earth
3 amp fused supply
Live
Neutral
Earth
3 amp fused supply
1
0
Live
2
Neutral
Earth

4.0 Electrical

4.1
Electrical Connections
230V 50Hz 12W (normal) 31W (boost)
NOTE: Wiring must be via a 3A fused
switched spur with a 3mm contact separation
in each pole. The wiring should be suitably
(BASEC or HAR) approved cable of
appropriate current carrying capacity.
For units switching to boost on operation of a light switch, an
in-line timer (order code TIM2) should be wired into the circuit
as shown below.
HR100R
Terminals
TIM2 Terminals
L
L
N
Automatic Control
The HR100R unit operates on continuous trickle ventilation.
Operation of switch turns unit to boost ventilation. When switch
is turned off units continue to operate on boost for a preset
period - adjustable 2-30 minutes.
The HR100R MUST NOT be wired in conjunction with a light
switch, units will fail.
HR100R
Terminals
Switched Live
L
1
L
2
Light
N
1
Mains via switched
0
fused spur
Light fitting if
2
Link
appropriate
L
Switched live
SL
Live
N
Neutral
Earth
Live
3 amp fused
supply
Neutral
Earth