Electrical - Vent-Axia HR300RW6 Operating, Installation And Servicing Instructions

Semi-remote wall mounted heat recovery ventilator

Advertisement

Plug
Fig. 7
Connection Spigot Plate
8
L E
N
Fig. 8
Heat Exchanger
Fig. 9

4.0 Electrical

4.1
Electrical Connections
230V 50Hz 100W max
1. Wiring must be via a 3A fused switched spur
with a 3mm contact separation in each pole. The
wiring should be suitably (Basec or Har)
approved cable of appropriate current carrying
capacity.
2. Ensure that the mains power supply is
isolated prior to installation.
3. Remove the plug from the socket and connect
incoming wires to the appropriate terminals
(Figs. 7 & 8).
4. Replace plug into socket.
5. Slide the heat exchanger into the unit (Fig. 9).
6. Locate the connection spigot plate on to the
front of the unit and secure with the four screws
provided (Fig. 9).
7. Connect ducting to the 150mm spigots.
NOTE: Ensure the controller to be used is
wired in accordance with the instructions
supplied with the controller.
8. Switch on the mains electrical supply and
check the operation of the unit.