2.0 Site Requirements

2.1
Information
1. The unit must be sited and connected by a
suitably qualified person and be in accordance
with current U.K. Building Regulations and
I.E.E. Wiring Regulations (BS 7671).
2. The unit is intended for permanent
connection to the mains electrical supply.
3. The HR100R is intended for fixed wiring
installation.
4. Ensure that the mains electrical supply is
compatible with the product's rating label.
5. The unit must be sited away from direct
sources of heat in excess of 40°C.
6. Do not site the ceiling diffusers in the vicinity
of excessive levels of airborne oil or grease.
7. If the ceiling diffusers are installed in a room
containing a fuel burning appliance, the installer
must ensure that air replacement is adequate
for both appliances.
8. The external grilles must be sited a minimum
of 500mm away from the flue of gas or open fire
appliances. This is to avoid back flow of gases
entering the room.
9. All safety regulations and requirements must
be strictly followed to prevent hazards to life and
property both during and after installation and
during subsequent maintenance or servicing.
10. Ensure the mains electrical supply is
isolated before commencing installation, or
maintenance.