Figure 7.
Sensor's minimum distance from an air vent
Abbildung 7. Mindestabstand des Fühlers zu Luftschlitzen
3.4. Changing the pre-set time
The pre-set time can be changed by means of the
DIP switches, which are located on the right side of
the unit's upper circuit board, as follows:
Figure 8.
DIP switches (Please note! 12 hours only for communal use/4 and 6 hours for family and communal use)
Abbildung 8. DIP-Schalter (Achtung! 12 h nur für gewerbliche und Vereinssaunen 4 h und 6 h für die Nutzung durch
Familien und gewerbliche bzw. Vereinssaunen)
3.5. Service instructions for the Harvia
control unit
The operation of the control units is shared be-
tween two electronic cards, which are connected
by means of a detachable flat cable.
The upper card is a display card (fig. 9), which
functions as a control and information device for
the user.
The lower card (fig. 10) functions as a an electric
power card, which houses 2 pcs C150 three-phase
contactors that conduct electrical power to the
heater (in the C90 control unit there are a safety
contactor and three power relays, in the C80/1
6
180°
DE
3.4. Änderung der Einschaltzeit
Die Änderung der Einschaltzeit erfolgt mit den DIP-
Schaltern, die sich folgendermaßen am rechten
Rand der oberen Schaltkarte des Steuergeräts be-
finden:
3.5. Wartungsanleitung für das
Harvia-Steuergerät
Die Funktionen der Steuergeräte sind auf zwei
im Gerät befindliche Elektronikplatten verteilt, die
miteinander durch einen entfernbaren Flachkabel-
anschluß verbunden sind.
Die obere Platte ist eine Anzeigeplatte (Abb. 9),
die dem Benutzer als Einstell- und Informationsge-
rät dient.
Die untere Platte (Abb. 10) dient zur Einstellung
der Leistung, über ihre 3-Phasen-Kontaktgeber
(C150; 2 Stk) wird die elektrische Leistung zum
Ofen geleitet (im Steuergerät C90 befinden sich