SLE / SLE-DP – SIMOLINK Encoder
5.3

PROFIBUS interface (X22 on SLE-DP)

CAUTION
NOTE
Siemens AG
GWE-477 763 4070.76 J
SIMOVERT MASTERDRIVES
02.2001
The interface between the SLE-DP and the PROFIBUS line is the
EN 50170-compliant 9-pin SUB D socket with screw locking
mechanism (UNC) on the front of the housing. It is labeled with the
designation X22 as well as "PROFIBUS" and the following symbol:
The interface supplies an electrically isolated, short-circuit-proof supply
voltage for the optional connection of an OLP (Optical Link Plug). All
PROFIBUS signals are isolated from the 24 V voltage supply (X1) and
the encoder signals (X21).
The connector hardware for both the encoder interface and the
PROFIBUS interface is a 9-pin SUB D socket. The two interfaces can
be distinguished only by their labeling and position (cf. Fig. 4-3). The
plug and socket must be connected correctly by the end-user during
installation.
Pin
Signal
1
2
3
RxD/TxD-P
4
CNTR-P
5
DGND
6
VP
7
8
RxD/TxD-N
9
Housing
Outer shield
9-pin SUB D socket with screw locking mechanism (UNC)
Table 5-4
Assignments of PROFIBUS interface connector (X22 on SLE-DP)
The cables must be connected by means of PROFIBUS connectors
since these contain the bus terminating resistors.
Fig. 5-3
Suitable PROFIBUS connectors
Operating Instructions
Meaning
Unused
Unused
PROFIBUS data - P (non-inverted) RS485
Control signal for PROFIBUS OLP
Ground for PROFIBUS data
Positive supply voltage for
terminating resistor and OLP
Unused
PROFIBUS data - N (inverted)
Unused
Connections
.
Range
n.c.
n.c.
TTL
0 V
DC + 5 V ± 10 %
for OLP
max. 100 mA
n.c.
RS485
n.c.
5-5