5.3

Supply voltage and cables

Please observe the informations about grounding and shielding in chapter 5.2.
5.3.1 ACS-2 plus 230 V version
Parameter
operating voltage range
mains frequency
power supply cable type

5.3.2 ACS-2 plus 12V version

Parameter
operating voltage range
current consumption
The door strike must be taken into consideration if its supply comes from the ACS-2 plus. The current
consumption of a door strike depends on the type, but lies somewhere between 200mA and 500mA.
The current consumption of an energized door strike must be known for each ACS-2 plus
when designing a 12V system.
The following drawing (powered on) shows the voltage drop of a 1.5mm
power consumption of 1A is calculated for each ACS-2 plus.
Observe the outgoing and return line.
Value
230 V AC –15% +10%
40 – 60 Hz
NYM 3 x 1,5 mm²
Value
10.0V to 15.0V DC
depends on the reader type, the number of readers and the interface type
cable compared to a 4mm
2
13
cable. A
2