15.6 Turnstile

The ACS-2 plus can manage, besides a standard door, 3 types of turnstiles. They differ from each other by
the number or the evaluation of the monitoring contacts.
Flow chart of a door monitoring with monitoring contacts to a "normal" door:
With the door closed, the monitoring contact is likewise closed. The respective alarm line recognizes the
necessary 12.1 KΩ, and thus a closed door. If the door is opened (A), the monitoring contact also opens and
signals that the door is open. The monitoring contact does not close until the door is closed again (B) and the
door is recognized as closed.

15.6.1 Turnstile with one monitoring contact

The door monitoring for a turnstile with a monitoring contact basically corresponds to a "normal" door.
In normal condition (with door closed) one of the contact makers A to D closes the monitoring contact (contact
maker A is used in the example).
Case 1)
Exterior reader enabled. "Door open" is signaled when the turnstile is activated in the left
rotational direction. Contact maker B closes the monitoring contact again. The door is
recognized as closed.
Case 2)
Interior reader enabled. In the right rotational direction, the monitoring contact is closed again
by contact maker D.
The rotational direction cannot be evaluated with this type. APB
used for the booking. If both sides are enabled, both persons are logged.
10
For details about BRE / APB (= Barring Repeated Entry / Antipassback), see the "Advanced functions of
MAfW"
(P32201-46-0G0-xx) and "Advanced functions of IQ MultiAccess" (P32205-46-0G0-xx).
10
is recognized on the reader