Honeywell ACS-2plus Installation Instructions Manual page 32

Table of Contents

Advertisement

32
The gray highlighted fields must be filled in
1. Calculation of the memory requirements for the cards
Header:
This is a preset value using 13 bytes for each card.
ID no.:
PIN-code:
Version no.:
R/T-zones:
1
Please observe the minimum and maximum values shown in the column no. of digits possible.
1
:
Enter the number of digits of the identification code to be used in the column no. of digits
required (e.g., 20 in case of 20-digit coding according to Novar or DIN).
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 7.5), the result must be rounded upwards
to the next integer (in this case, to 8) and entered in the column rounded to the next
integer.
Enter the number of digits of the PIN code to be used in the column no. of digits required
(the PIN code may comprise min. 4 and max. 8 digits).
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 2.5), the result must be rounded upwards
to the next integer (in this case, to 3) and entered in the column rounded to the next
integer.
Enter the number of digits of the version number to be used in the column no. of digits
required. In the case of contactless cards, a unique number comprising 20 digits is used.
In this case, no version number is required (input = 0). In all other cases, the version
number may comprise 2 digits. It is recommended to enter 2.
Divide this number by 2 (the required number of bytes results) and enter the result in the
column value.
If the result of the division is no integer (e.g., 0.5), the result must be rounded upwards
to the next integer (in this case, to 1) and entered in the column rounded to the next
integer.
Enter the number of room/timezones required. Divide this amount by 8 and round to the
next integer. The ACS-2 plus will store only the room/time zones which are allocated to
doors controlled by this controller.
Installation instructions / ACS-2 plus