Nibe F1245 Series Installation Manual page 50

Ground source heat pump
Hide thumbs Also See for F1245 Series:
Table of Contents

Advertisement

min. allowed speed
Setting range: 1 - 50%
Default values: 1 %
max. allowed speed
Setting range: 50 - 100 %
Default values: 100 %
speed active cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
speed passive cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
Set the speed at which the heating medium pump is to
operate in the present operating mode. Select "auto" if
the speed of the heating medium pump is to be regu-
lated automatically (factory setting) for optimal operation.
If "auto" is activated for heating operation you can also
make the setting "max. allowed speed" which restricts
the heating medium pump and does not allow it to run
at a higher speed than the set value.
For manual operation of the heating medium pump,
deactivate "auto" for the current operating mode and set
the value to between 0 and 100% (the previously set
value for "max. allowed speed" no longer applies).
"heating" means heating operating mode for the heating
medium pump.
"speed in wait mode" means heating or cooling operating
mode for the heating medium pump, but when the heat
pump requires neither compressor operation nor electric
additional heat and slows down.
"hot water" means hot water operating mode for the
heating medium pump.
"pool" (accessory required) means pool heating operating
mode for the heating medium pump.
"cooling" (accessory required) means operating mode
cooling for the heating medium pump.
If there are accessories for cooling present or if the heat
pump has a built-in function for cooling you can also set
the heating medium pump speed during active respect-
ively cooling operating modes (the heating medium
pump then runs in manual operation).
50
Chapter 8 | Control - Menus
MENU 5.1.12 - INTERNAL ELECTRICAL
ADDITION
max connected el. add.
Setting range: 7 / 9
Default value: 7
set max electrical add.
Setting range: 0 - 9 kW
Factory setting: 6 kW
fuse size
Setting range: 1 - 200 A
Factory setting: 16 A
transformation ratio
Setting range: 300 - 3000
Factory setting: 300
Here you set the max. electrical output of the internal
electrical addition in F1245 and the fuse size for the in-
stallation.
Here you can also check which current sensor is in-
stalled on which incoming phase to the property (this
requires current sensors to be installed, see
Check by marking "detect phase order" and pressing the
OK button.
The results of these checks appear just below the menu
selection "detect phase order".
MENU 5.1.14 - FLOW SET. CLIMATE SYSTEM
presettings
Setting range: radiator, floor heat., rad. + floor heat.,
DOT °C
Default value: radiator
Setting range DOT: -40.0 – 20.0 °C
Factory setting DOT: -18.0 °C
own setting
Setting range dT at DOT: 0.0 – 25.0
Factory setting dT at DOT: 10.0
Setting range DOT: -40.0 – 20.0 °C
Factory setting DOT: -18.0 °C
The type of heating distribution system the heating
medium pump (GP1) works towards is set here.
dT at DOT is the difference in degrees between flow
and return temperatures at dimensioned outdoor tem-
perature.
page
27).