Nibe F1245 Series Installation Manual page 49

Ground source heat pump
Hide thumbs Also See for F1245 Series:
Table of Contents

Advertisement

MENU 5.1.9 - BRINE PUMP SPEED
op. mode
Setting range: auto / manual / fixed delta
Default value: auto
delta T
Setting range: 2 - 10 °C
Factory setting: 4 °C
speed in wait mode
Setting range: 1 - 100 %
Factory setting: 70 %
Speed extern. contr. (AUX)
Setting range: 1 - 100 %
Factory setting: 100 %
manual
Setting range: 1 - 100 %
Factory setting: 100 %
speed passive cooling (accessory is required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed active cooling (accessory is required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed in wait mode cooling
Setting range: 1 - 100 %
Factory setting: 30 %
temperature difference, active cooling
Setting range: 2 - 10 °C
Factory setting: 5 °C
Set the speed of the brine pump here. Select "auto" if
the speed of the brine pump is to be regulated automat-
ically (factory setting) for optimal operation.
For manual operation of the brine pump, deactivate
"auto" and set the value to between 1 and 100 %.
For operation of brine pump with "fixed delta", select
"fixed delta" under "op. mode" and set the value between
2 and 10 °C.
NIBE F1245
If there are accessories for cooling, you can also set the
brine pump's speed during passive cooling operation
here (the brine pump then runs in manual operation).
This menu is also set in the slave heat pump's limited
menu system.
MENU 5.1.10 - OP. MOD HEAT MED PUMP
op. mode
Setting range: auto, intermittent
Default value: auto
Set the operating mode of the heating medium pump
here.
auto: The heating medium pump runs according to the
current operating mode for F1245.
intermittent: The heating medium pump starts approx.
20 seconds before, and stops at the same time as, the
compressor.
MENU 5.1.11 - PUMP SPEED HEATING
MEDIUM
Operating status
Setting range: auto / manual
Default value: auto
Manual setting, hot water
Setting range: 1 - 100 %
Factory setting 6 kW: 40 %
Factory setting 8 kW Enamel: 55 %
Factory setting 8 kW Copper/Stainless steel: 40 %
Factory setting 10 kW Enamel: 70 %
Factory setting 10 kW Copper/Stainless steel: 55 %
Factory setting 12 kW Enamel: 100 %
Factory setting 12 kW Copper/Stainless steel: 70 %
Manual setting, heating
Setting range: 1 - 100 %
Default values: 70 %
Manual setting, pool
Setting range: 1 - 100 %
Default values: 70 %
speed in wait mode
Setting range: 1 - 100 %
Default values: 30 %
Chapter 8 | Control - Menus
49

Advertisement

Table of Contents
loading

Table of Contents