8.3

Luminaires settings

In the "Settings" menu, additional information (location, info text) can be assigned to
luminaires. Using the "Test" command the status of the luminaire can be checked
immediately.
Notes
The assignment of the luminaires must be completed before defining the
luminaires settings (refer to section 8.4 on page 42).
The operating mode can be set to "Maintained mode", "Non-maintained mode" or
"Switched maintained light".
The display of the luminaires is identical to the display in the "Status" menu (refer
to section 8.2 on page 39).
There are two possibilities to configure the
luminaires:
• all luminaires in a group
(the existing settings of all the
luminaires in the selected group are
overwritten)
• each luminaire separately
To configure only one luminaire, press the
corresponding luminaire symbol. If all
luminaires within a group should have the
same values, press the reference text
(e.g. Group1).
Notes
Safety luminaires equipped with PC Emergency + EMC module can only be
operated in maintained mode.
The feature "switched maintained light" is only available, if an ONLITE local
Switch Module is installed. In the operating mode "switched maintained light" the
pushbutton inputs act as follows:
• Pushbutton input S1 acts on group 1 or individual luminaires in group 1.
• Pushbutton input S2 acts on group 2 or individual luminaires in group 2.
• Pushbutton input S3 acts on group 3 or individual luminaires in group 3.
• Pushbutton input S4 acts on group 4 or individual luminaires in group 4.