The detail view shows the start and
the end time of the test, the reason for the
test, the overall result and the errors that
occurred for each luminaire.
The luminaires errors are summarised
according to the group in which they are
installed.
Additionally, the number of luminaires
currently installed within the groups is
displayed.
7.3
Automatic function test
The function test tests the emergency luminaires by briefly switching to emergency mode.
A desired time and day can be programmed for function tests to be automatically carried
out. These settings (day/time) can either be the same for all groups or entered separately
for each group.
In case these settings are different for each group, each of them has its own tab. Manual
starting the function test is recommended during initial commissioning or if new
components are added to the emergency lighting system or other changes are carried
out on the emergency lighting system (e.g. replacement of luminaires, changes to the
configuration).
Notes
No automatic function test can be executed while the system is blocked or if a test
is still running (e.g. after starting it manually). In this case, the automatic test is
delayed by one day (until the set time of day is matching). An error message
appears when attempting to start the test manually while the system is blocked.
Battery faults can only be eliminated by performing a "duration test".
ONLITE local SB 128 Controller