Automatic Duration Test - Zumtobel ONLITE local SB 128 Controller Operating Instructions Manual

Table of Contents

Advertisement

Starting the function test
All groups similar: If this checkbox is
selected, the adjusted time settings are
applied to all groups.
Weekdays: Press on the field and select
the desired day by marking the
corresponding checkbox.
Time: Press on the field and edit the value
using the provided arrow keys.
Start function test now: Press this key to immediately start the function test
(duration: approx. 5 minutes).
See also test book: View the last function test entry by pressing this key (refer
to section 7.2 on page 34).
Function test started
The following information is displayed
while the function test is running:
• Start date and time.
• Type of activation:
"Manual release": manual test.
"Programmed time": automatic test.
• Progress of the running function test
(indicated in hours and minutes).
Cancel test
Press this key to abort the running function test.
7.4

Automatic duration test

During the duration test, the batteries of all connected luminaires are discharged until their
nominal operation time (between 1 and 3 hours, depending on the battery type) has
elapsed. If the nominal operation time can not be reached, the error message "Battery
fault" appears. The test is executed as long as the nominal operation time or the
permissible limit operation time of the battery is exceeded (cut-off voltage reached or
deep-discharging protection activated) or until the test is aborted manually.
To carry out duration tests automatically, a day, the desired months and the time can be
programmed (e.g. at 23:00 on the 15th of January, April, July and October). These settings
can either be the same for all groups or entered separately for each group (in this case
each group has its own tab).
It can also be selected whether the duration test of the respective group is to be carried
out for luminaires with even numbers and/or for luminaires with odd numbers.
36
ONLITE local SB 128 Controller

Advertisement

Table of Contents
loading

Related Products for Zumtobel ONLITE local SB 128 Controller

This manual is also suitable for:

22 156 829