[5-1 Dipswitch Functions and Factory Settings ]
5-1-2

Indoor Unit Switch Functions and Factory Settings

(1) Dipswitches
1) SW1,3
Switch
Function
-
1
2
Clogged filter detection
3
Filter check reminder
time setting
-
4
5
Remote display option
SW1
-
6
-
7
8
-
9
External input
10
Operation switching
Model setting
1
2
Capacity code
-
3
-
4
-
5
SW3
6
-
LEV setting conversion
7
function
-
8
-
9
-
10
Reset of the integrated
operation time
1
Valid/Invalid (fan belt)
Reset of the integrated
SW7
operation time
2
Valid/Invalid (fan motor)
-
3
-
4
Note 1. Setting timing for DIPSW 1 and 3 is during unit stoppage (remote controller OFF). It is not necessary to reset the settings by power-off.
Note 2. Settings in the shaded areas are factory settings.
6
- chapter 5
Function according to switch setting
OFF
ON
-
-
Not available
Available
100h
2500h
-
-
Fan output
Thermo-ON signal
-
-
-
-
-
-
Level
Pulse
External input
MA remote controller
-
-
Refer to the combination with SW2
-
-
-
-
-
-
-
-
Not available
Available
-
-
-
-
-
-
Not available
Available
Not available
Available
-
-
-
-
Switch setting timing
OFF
ON
While the unit is stopped
(Remote controller OFF)
Notes