[5-2 Outdoor Unit Control ]
(2) Ending the emergency operation
1) End conditions
When one of the following conditions is met, emergency operation will end.
When an error is reset
*When resetting an error with the remote controller or the external input
When an error is detected that does not allow the unit to run the emergency operation.
2) Miscellaneous
When encountering problems other than the ones listed above, the system makes an error stop without performing emergen-
cy operation. (Only the indoor fan operates unless problems are found with the fan.)
When problems are found in only one of the two units of a 2-refrigerant circuit, only the unit with the problems will run an
emergency operation or stop its operation, and the other unit will keep running its operation.
Emergency operation is intended only as a first aid until the unit is serviced. Have the unit serviced without delay to restore a
normal operation.
2. Communication circuit failure or when some of the outdoor units are turned off
Emergency operation mode will not be performed if a fault occurs in internal/external communication or OC-OS communica-
tion.
5-2-14
Operation Mode
(1) Indoor unit operation mode
The operation mode can be selected from the following 3 modes using the remote controller.
1
Cooling mode
2
Fan mode
3
Stopping mode
(2) Outdoor unit operation mode
1
Cooling mode
2
Stopping mode
5-2-15
Demand Control
Cooling operation can be prohibited (Thermo-OFF) by an external input to the indoor units.
When DIP SW6-8 is set to ON, the 4-step DEMAND control is enabled.
Eight-step demand control is possible in the system with two outdoor units.
For details, refer to the following page(s). [2-4-7 Various Control Methods Using the Signal Input/Output Connector on Outdoor
Unit]
BS_05_C
All indoor units in operation are in cooling mode.
All indoor units are in fan mode or stopping mode.
15