Mitsubishi Electric PUHY-P250YNW-A Service Handbook page 272

Hide thumbs Also See for PUHY-P250YNW-A:
Table of Contents

Advertisement

[8-14 Replacement Instructions for Motor and Bearing (Indoor Unit) ]
(2) Attach the V-belt, and temporarily tighten the Bolt 1 (two places).
(3) Tighten the Bolt 2 so that the V-belt tension is proper, and then tighten the Bolt 1.
Refer to the following table for the V-belt tension.
Belt tension
Model Name
PFD-P250VM-E
PFD-P500VM-E
(4) Reconnect the motor wiring.
BS_08_C
Power source
Deflection
frequency
force
[Hz]
W [N]
50
15.5~16.5
60
14.5~15.5
50
20.0~22.5
60
19.5~21.0
Amount of
deflection
L [mm]
5.0~5.5
5.0~5.5
5
4.5~5.0
73