Carrier AquaForce 30XV140-500 Installation Instructions Manual page 112

Variable speed air-cooled liquid chillers with greenspeed intelligence
Hide thumbs Also See for AquaForce 30XV140-500:
Table of Contents

Advertisement

Table 12 — 30XV140-500 Electrical Data, Single Point Power, High Tier, Variable Speed Fans
UNIT VOLTAGE
UNIT
Supplied
30XV
V(3 Ph)
Hz
Min
208/230
60
187
380
60
342
400
60
360
460
60
414
575
60
518
140
380
50
342
400
50
360
415
50
374
440
50
396
208/230
60
187
60
342
380
400
60
360
460
60
414
575
60
518
160
380
50
342
400
50
360
415
50
374
440
50
396
208/230
60
187
380
60
342
400
60
360
460
60
414
575
60
518
180
380
50
342
400
50
360
415
50
374
440
50
396
208/230
60
187
380
60
342
400
60
360
460
60
414
575
60
518
200
380
50
342
400
50
360
415
50
374
440
50
396
380
60
342
400
60
360
460
60
414
575
60
518
225
380
50
342
400
50
360
415
50
374
440
50
396
380
60
342
400
60
360
460
60
414
575
60
518
250
380
50
342
400
50
360
415
50
374
440
50
396
LEGEND
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
VFD
— Variable Frequency Drive
NOTES:
1. Units are suitable for use on electrical systems where voltage
supplied to the unit terminals is not below or above the listed
minimum and maximum limits. Maximum allowable phase imbal-
ance is: voltage, 2%; amps 10%.
2. Evaporator heater (where applicable) is wired into the control cir-
cuit so it is always operable as long as the control power supply
disconnect is on, even if any safety device is open.
3. For MCA that is less than or equal to 380 amps, 3 conductors are
required.
For MCA between 381-760 amps, 6 conductors are required.
For MCA between 761-1140 amps, 9 conductors are required.
For MCA between 1141-1520 amps, 12 conductors are required.
Calculation of conductors required is based on 75 C copper wire.
STANDARD CONDENSER FANS
NUMBER OF
COND FANS
MCA
Max
253
10
560.2
418
10
306.6
440
10
292.7
506
10
252.9
633
10
203.3
418
10
314.4
440
10
300.5
457
10
289.7
484
10
273.4
253
12
646.7
418
12
355.3
440
12
336.4
506
12
291.9
633
12
234.9
418
12
363.2
440
12
346.6
457
12
335.4
484
12
316.3
253
12
853.7
418
12
467.8
440
12
381.4
506
12
330.1
633
12
264.2
418
12
478.0
440
12
454.6
457
12
438.9
484
12
415.3
253
14
802.7
418
14
440.0
440
14
418.3
506
14
362.2
633
14
290.6
418
14
450.4
440
14
428.7
457
14
414.9
484
14
390.8
418
14
491.1
440
14
468.0
506
14
405.4
633
14
325.5
418
14
501.9
440
14
477.4
457
14
462.1
484
14
435.2
418
16
555.7
440
16
529.1
506
16
458.4
633
16
367.7
418
16
568.7
440
16
541.9
16
523.2
457
484
16
494.1
HIGH STATIC CONDENSER FANS
REC FUSE
MOCP
MCA
SIZE
700
700
573.1
400
350
319.5
350
350
305.3
300
300
263.9
250
225
211.9
400
350
327.6
400
350
313.0
350
350
300.5
350
300
282.4
800
800
662.2
450
400
370.8
450
400
351.4
350
350
305.1
300
300
245.3
450
400
379.1
450
400
361.6
450
400
348.7
400
350
327.6
1000
1000
869.2
600
600
483.3
500
450
396.4
450
400
343.3
350
300
274.5
600
600
493.8
600
500
469.6
600
500
453.4
500
500
429.0
1000
1000
820.8
500
500
458.1
500
500
435.9
450
400
377.6
350
350
302.6
600
500
468.9
500
500
446.3
500
500
431.8
500
450
406.8
700
600
509.3
600
600
485.6
500
500
420.8
450
400
337.5
700
600
520.3
600
600
495.0
600
600
479.0
600
500
451.2
700
700
576.5
700
600
549.2
600
600
476.0
500
450
381.5
700
700
589.8
700
600
562.0
700
600
542.6
600
600
512.3
4. Based on the operational characteristics of a VFD, the "inrush"
current normally associated with a chiller is limited and will be
lower than the MCA rating of the chiller.
5. Wiring for main field supply must be rated 75 C minimum. Use
copper for all units. Refer to Table 8 for power entry option.
6. MCA and MOCP values shown are inclusive of control power
transformer loads.
112
CONTROL CIRCUIT
Voltage
REC FUSE
MOCP
1 PH,
SIZE
60 Hz
700
700
115
400
350
115
400
350
115
350
300
115
250
250
115
400
400
115
400
350
115
400
350
115
350
350
115
800
800
115
450
450
115
450
400
115
400
350
115
300
300
115
500
450
115
450
400
115
450
400
115
400
400
115
1000
1000
115
600
600
115
500
450
115
450
400
115
350
300
115
600
600
115
600
600
115
600
500
115
500
500
115
1000
1000
115
600
500
115
500
500
115
500
450
115
400
350
115
600
600
115
600
500
115
500
500
115
500
450
115
700
600
115
600
600
115
600
500
115
450
400
115
700
600
115
700
600
115
600
600
115
600
500
115
700
700
115
700
600
115
600
600
115
500
450
115
800
700
115
700
700
115
700
600
115
600
600
115
MCA
and
MOCP
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
40
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60
60