Stopping/Restarting Chiller Operation

You can start or stop the chiller from the Tracer® AdaptiView™ display by using the Auto and
Stop buttons. The buttons are located in upper right.

Stopping the Chiller

You can stop the chiller in two ways:
To stop the chiller in either of these ways:
1. Touch the Stop button to initiate the chiller shutdown process. A confirmation screen appears
2. Touch the Y Y e e s s button. The Shutting Down Chiller screen appears as shown in the following
18
Normally, which involves stopping the various components sequentially in order to protect
them from damage
Immediately, which shuts down all the components at once, and should be used only in an
emergency
as shown in the following figure.
Figure 6. Stop the Chiller confirmation screen
figure.
To stop the chiller normally, no further action is required. You can observe the submodes
change and the timers count down.
To stop the chiller immediately, touch the I I m m m m e e d d i i a a t t e e S S h h u u t t d d o o w w n n button.
To cancel shutdown, touch the C C a a n n c c e e l l S S h h u u t t d d o o w w n n button.
CTV-SVU01G-EN