Application example
Switch-on point = 2000 W, switch-off point = 1800 W
If the inverter is outputting 2000 W or above, then the floating switch contact on the
inverter is switched on.
If the inverter output falls to below 1800 W, the floating switch contact is switched off.
Possible applications:
Operating a heat pump or an air-conditioning system using as much self-generated
power as possible

Time / Date

Set the time, date and automatic changeover between summer and winter time
Setting range
Set time
Set the time (hh:mm:ss or hh:mm am/pm – depending on the setting for the time display
format)
Set date
Set the date (dd.mm.yyyy or mm/dd/yyyy - depending on the setting for the date display
format)
Time display format
For specifying the time display format
Setting range
Factory setting
Date display format
For specifying the date display format
Setting range
Factory setting
Summer/winter time
Activate/deactivate automatic changeover between summer and winter time
Setting range
Factory setting
IMPORTANT! The time and date must be set accurately in order for the day and year
values and for the day characteristic to be displayed correctly.

Display settings

Setting range
Language
Set language for display
54
Set time / Set date / Time display format / Date display
format / Summer/winter time
12hrs / 24hrs
Depends on country setup
mm/dd/yyyy / dd.mm.yy
Depends on country setup
on / off
on
Language / Contrast / Illumination