Status Codes - Class - Fronius Symo Hybrid 3.0-3-S Operating Instructions Manual

Grid-connected inverter, energy package
Hide thumbs Also See for Symo Hybrid 3.0-3-S:
Table of Contents

Advertisement

Code
Description
143
Emergency power overload
144
Emergency power short-cir-
cuit
145
Status code 143 or 144 has
occurred more than three
times
Status codes –
Class 3 includes status codes that may occur while feeding energy into the grid, but gen-
Class 3
erally do not cause the process to be interrupted for any length of time.
The inverter disconnects automatically from the grid, the grid is then monitored as spe-
cified and the inverter attempts to resume feeding energy into the grid.
Code
Description
301
Overcurrent (AC)
Overcurrent (DC) or battery not
302
detected
303
DC module overtemperature (PV)
304
AC module overtemperature
305
No power being fed in, despite
closed relays
There is not enough PV power
available for feeding energy into the
306
grid and no power has been
requested from the battery.
DC low
DC input voltage too low for feeding
307
energy into the grid
IMPORTANT! Due to the low level of insolation early in the morning and in the evening, the status codes 306
(Power low) and 307 (DC low) are displayed routinely at these times of day. These status codes do not indic-
ate any kind of fault.
308
Intermediate circuit voltage too high
309
PV input voltage too high
313
Battery input voltage too high.
122
Behaviour
Emergency power mode is
interrupted. The inverter
attempts to start emergency
power mode three times; if
this is unsuccessful status
code 145 is displayed
Behaviour
Short-term interruption while
feeding energy into the grid.
The inverter repeats its start-
up routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine.
Short-term interruption while
feeding energy into the grid.
The inverter repeats its star-
tup routine. This service code
may occur sporadically even
though there is no actual
fault.
Remedy
Check emergency power cir-
cuit; if this status code keeps
recurring, contact your sys-
tem fitter
Remedy
*)
Purge cooling air
openings and heat
sink; **)
**)
Wait for sufficient insol-
ation; wait for an
energy management
command;
**)
Wait for sufficient insol-
ation;
**)
**)
Switch on, connect or
check battery;
*)