4.10 Controller Function Codes; Table 4-5 Controller Function Codes - Carrier Transicold 69NT40-561-001 Operation And Service Manual

Container refrigeration units
Hide thumbs Also See for Transicold 69NT40-561-001:
Table of Contents

Advertisement

Config
Title
CnF45
Low Humidity Enabled
CnF46
Quench/liquid Injection Valve Type
CnF47
Vent Position
CnF49
OEM Reset Option
CnF50
Enhanced Bulb Mode Interface
CnF51
Timed Defrost Disable
CnF52
Oil Return Algorithm
CnF53
Water Cool Oil Return Logic
CnF55
TXV Boost Relay
CnF56
TXV Boost Circuit
CnF57
PWM Compressor Control
CnF59
Electronic Evaporator Expansion Valve
CnF61
ACT ASC Control Enable
CnF62
Extended Temperature Control Enable
CnF63
CCPC Pre-trip/Tripstart Default State
CnF64
Enable Fan Pulsing Logic
CnF66
High Speed Evaporator Fan Option
CnF67
Air Heaters
Configuration numbers not listed are not used in this application. These items may appear when loading
configuration software to the controller but changes will not be recognized by the controller programming.

4.10 Controller Function Codes

Code
Title
Display Only Functions - Cd01 through Cd26 are display only functions.
Cd01
Digital Unloader
Valve Closed (%)
Cd03
Compressor Motor
Current
Cd04
Line Current,
Phase A
Cd05
Line Current,
Phase B
Cd06
Line Current,
Phase C
Cd07
Main Power Voltage
Table 4–4 Controller Configuration Variables
Table 4–5 Controller Function Codes
Description
Note: If the function is not applicable, the display will read "-----"
Displays the DUV percent closed. The right display reads 100% when the valve
is fully closed. The valve will usually be at 10% on start up of the unit except in
very high ambient temperatures.
The current sensor measures current draw in lines L1 & L2 by all of the high volt-
age components. It also measures current draw in compressor motor leg T3. The
compressor leg T3 current is displayed.
The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for con-
trol and diagnostic purposes. For control processing, the highest of the Phase A
and B current values is used for current limiting purposes. For diagnostic pro-
cessing, the current draws are used to monitor component energization.When-
ever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to deter-
mine if it falls within the expected range of values for the component. Failure of
this test will result in a Pre-trip failure or a control alarm indication.
The main supply voltage is displayed.
Default
Out
nO=0=no
OFF
OFF
0
0
0
0
0
0
0
0
0
0
0
0
0
0
NOTE
4–25
Option
In
nC=1=nc
UP, LOW, CUStOM
0-off,1-std, 2-spec, 3-cust
0-out, 1-in
0-out, 1-in
0-out, 1-in
0-out, 1-in
0-out, 1-in
0-out, 1-in
0-out, 1-in
0-out, 1-EC, 2-KE, 3-NA
0-out, 1-in
0-out, 1-in
0-on, 1-off
0-in, 1-out
0-off, 1-on
0-out, 1-in
T-340