Figure 7.7 Water-Cooled Condenser Cleaning, Forced Circulation - Carrier Transicold 69NT40-561-001 Operation And Service Manual

Container refrigeration units
Hide thumbs Also See for Transicold 69NT40-561-001:
Table of Contents

Advertisement

Figure 7.7 Water-Cooled Condenser Cleaning, Forced Circulation

3
2
1
1) Pump support
2) Tank
3) Suction
4) Pump
5) Priming Connection (Centrifugal pump
50 gpm at 35' head)
6) Globe valves
6. Allow the Oakite No. 32 solution to soak in the tube coils for several hours, periodically pump-circulating it with
an acid-proof pump.
An alternate method may be used whereby a pail (see
coils by a hose can serve the same purpose by filling and draining. The solution must contact the scale at
every point for thorough de-scaling. Air pockets in the solution should be avoided by regularly opening the
vent to release gas. Keep flames away from the vent gases.
7. The time required for de-scaling will vary, depending upon the extent of the deposits. One way to determine
when de-scaling has been completed is to titrate the solution periodically, using titrating equipment provided free
by the Oakite Technical Service representative. As scale is being dissolved, titrate readings will indicate that the
Oakite No. 32 solution is losing strength. When the reading remains constant for a reasonable time, this is an
indication that scale has been dissolved.
5
4
- - - - -
NOTE
It is important to provide a vent at the top for escaping gas.
7
6
8
10
11
12
7) Vent
8) Close vent pipe valve when pump is
running
9) Condenser
10) Remove water regulating valve
11) Return
12) Fine mesh screen
Figure
7.8) filled with the solution and attached to the
7–13