Installation instructions
Step 2 – Install Chiller
2.1 Positioning
The chiller must be placed in a hygienically suitable environment, on
a surface capable of bearing the weight of the machine complete with
water. Do not place close to direct or indirect heat sources (ovens,
stoves, radiators, etc.).
Locate close to electricity and water supply points. Ensure the
power cable and water hose do not form an obstruction. The water
connections and condenser need to be accessible for maintenance.
Protect from water splashes and place in a location with the
temperature appropriate to the climate class stated on the EC
nameplate, otherwise malfunctions may occur and warranty rights are
forfeited.
2.2 Ventilation
Allow a minimum clearance of 200mm around the back, top and
sides of the chiller unit.
For installation in an enclosed single cupboard, the vent kit and a
double auxiliary fan kit (part no 93159) must be installed.
• Install the kickboard vent grille for external air intake.
• Install the fan at the top of the cupboard to extract hot air out of
the cupboard (requires additional electrical power outlet).
• Cut-out in the cabinet floor.
For installation in an enclosed, double cupboard, the minimum
ventilation requirement is:
• Perforated or expanded metal door with at least 60% open area
• 2x cut-outs in the cabinet floor to provide air intake.
If ventilation is insufficient, additional vents and fans may be installed
as optional extras. Contact Zenith service for details.
EC climate classes:
SN - For ambient temperatures from 10°C to 32°C
N - For ambient temperatures from 16°C to 32°C
ST - For ambient temperatures from 18°C to 38°C
T - For ambient temperatures from 18°C to 43°C
2.3 Overflow connection
Check the overflow connector is not obstructed. Use a tube to
connect the overflow drainage connector (A) from the tank to a
drainage point or a large container (not supplied).
A tundish to comply with AS3500 may be required if the unit is
installed in a cupboard, or in an area not utilising a floor waste.
805812NZ v1.04 05.20 HydroChill Install Instructions