Vertical Through-The-Roof Applications - Vermont Castings Chateau DVT38 Installation Instructions And Homeowner's Manual

Direct vent decorative gas appliance
Table of Contents

Advertisement

Chateau™
Sealing firestop gaps with high temperature sealant
will restrict cold air being drawn in around fire-
place.
STEP 8
Guide the vent terminations 8" and 11" collars into their
respective vent pipes. Double check that the vent pipes
overlap the collars by 2" (50mm). Secure the termina-
tion to the wall with screws provided and caulk around
the wall plate to weatherproof. (Fig. 26) As an alterna-
tive to screwing the termination directly to the wall you
may also use expanding plugs or an approved exterior
construction adhesive.
Support horizontal pipes every 3ʼ (91 cm)
with metal pipe straps.
Check fireplace to make sure it is levelled
and properly positioned.
Fig. 26 Secure termination to wall.
Vertical Through-the-Roof
Applications
Use of Restrictor Plate
for Vertical Venting Applications
The primary purpose for the vent restrictor is to regain
flame height under certain venting conditions as
outlined below.
NOTE: The joints of the inner pipe (flue pipe) must be
taped with 550°F or higher temperature metal adhesive
tape that meets the requirements of F.A.R. 25.853(a)
High temperature sealant milpack or stove cement
of 550°F or higher could be used instead. The joints
of The outer pipe (fresh air pipe) must be taped with
315°F or higher temperature metal adhesive tape or the
use of high temperature milpack or stove cement would
be applicable. When using the unitized 30°, 45° or 90°
elbows, apply 1/4" bead of high temperature, 550°F or
higher, sealant (milpack or stove cement) to the joint of
the inner pipe (flue pipe) and the straight section as it is
16
impossible to be taped. The outer pipe must be taped
with 315°F high temperature metal adhesive tape for
proper sealing.
For vertically venting either propane or natural gas
units, with vertical vent heights of 12ʼ (3.7m) or greater,
(measured from the top of the flue collar) the restrictor
plate as supplied with this unit should be used. (Fig.
27) Also, the fresh air restrictor plate could be adjusted
according to your vent height. (Fig. 27) Refer to Pages
20 & 21, Figures 36 & 38 for restrictor plate installation
and fresh air restrictor plate adjustment.
DVT44 - Natural or LP
DVT38 - Natural or LP
Fresh Air Restrictor Plate
X
30ʼ to 40ʼ
20ʼ to 29ʼ
12ʼ to 19ʼ
Fig. 27 Restrictor plate use in straight up installation.
For vertical venting configurations that include a
minimum vertical rise of 12ʼ (3.7m) and a maximum
horizontal offset of 10ʼ (3m) the 4¹⁄₂" restrictor plate
supplied with this unit should be used. The fresh air
restrictor plate could be adjusted to the setting #3
FP1243a
(DVT44 Only). (Fig. 28) Refer to Pages 20 & 21,
Figures 36 & 38 for restrictor plate installation and fresh
air restrictor plate adjustment.
Natural or LP
Use 4���"
Fig. 28 Restrictor plate use with horizontal offset.
12'
(3.7m)
Use 6���"
or Greater
'X'
Use 5���"
Setting
#1
#2
#3
FP1409
restrictor plate
straight up installation
8/26/03 djt
10' (3m) Max.
Fresh Air Restrictor Plate
Setting = None or #3 Only
FP1410
Restrictor plate
horizontal offset installation
8/26/03 djt
FP1409
12'
(3.7m)
Min. Rise
FP1410
20006081