United Technologies Carrier 30RQM 160 Installation, Operation And Maintenance Instructions page 53

Reversible air-to-water heat pump
Table of Contents

Advertisement

10 - OPTIONS
10.7.6 - Installation
The water supply of each desuperheater is arranged in parallel.
The  water  connections  on  the  desuperheater  water  inlets  and 
outlets must not cause any mechanical local constraint at the heat
exchangers. If necessary, install flexible connection sleeves.
Install  water  flow  control  and  balancing  valves  at  the  heat 
exchanger outlet. Water flow control and balancing can be done 
by reading the pressure drop in the heat exchangers. This pressure 
drop must be identical on all of them with the total water flow rate 
given by the "Electronic catalogue" selection program.
Refer to the pressure drop curves below to perform the adjustment 
of  the  balancing  valves  before  starting  up  the  installation.  It  is 
possible  to  fine-tune  the  variable  water  flow  control  for  each 
desuperheater when the unit is running at full load, attempting to 
obtain outlet water temperatures which are completely identical 
on each circuit.
Desuperheater
(plate heat exchanger pressure drop curves)
100
10
1
0.1
Heat exchanger water flow rate, l/s
Heat exchanger water flow rate, l/s
1
Circuit with 1 compressor
2
Circuit with 2 compressors
3 
Circuit with 3 compressors
4
Circuit with 4 compressors
Operation of the pump (see typical diagram - item 20 of chapter 
10.7.5) of the desuperheater water circuit can be linked to:
1-  The start-up of the first compressor of the unit : terminal block 
37/38 
2-  The heat water need : Output DO-01 terminal block n°491/492 
of the EMM board (option 156)
A dedicated flow switch (item 29) can also be installed to generate 
an alarm if there is a problem with the pump (customer control 
system).
The volume of the desuperheater circuit water loop must be as 
low as possible so that the temperature can increase rapidly when 
the unit is started up. The minimum entering water temperature 
at the desuperheater is 25°C. A three-way valve (item 31) may be 
necessary with a controller, as the sensor controlling the minimum
temperature requires water at the inlet.
The desuperheater water loop must include a damage limitation 
accessory in case of a fire and an expansion tank. When selecting 
these,  consider  the  water  loop  volume  and  the  maximum 
temperature (120°C) when pump operation is stopped (item 20).
1
2
3
4
1
10.7.7 - Operating range
Cooling mode
Water heat exchanger (evaporator)
Entering water temperature at start-up
Leaving water temperature during operation
Entering water temperature at shut-down
Desuperheater
Entering water temperature at start-up
Leaving water temperature during operation
Entering water temperature at shut-down
Air heat exchanger (condenser)
Entering air temperature
Available static pressure
Heating mode
Water heat exchanger (condenser)
Entering water temperature at start-up
Leaving water temperature during operation
Entering water temperature at shut-down
Desuperheater
Entering water temperature at start-up
Leaving water temperature during operation
Entering water temperature at shut-down
Air heat exchanger (evaporator)
Entering air temperature
Available static pressure
Note: Do not exceed the maximum operating temperature.
(1)  For an application that requires operation below 6.8°C, contact Carrier.
(2)  The entering water temperature at start-up must not be lower than 25°C. For 
installations with a lower temperature a three-way valve is necessary.
(3)  For operation down to -20°C the unit must be equipped with option 28 (winter 
operation). In addition the unit must either be equipped with the frost protection 
option  or  the  water  loop  must  be  protected  by  the  installer  by  adding  a  frost 
protection solution.
Maximum outside temperatures: During  storage  and  transport  of  the 
10
30RQM/30RQP units the minimum and maximum temperatures must not exceed 
-20°C  and  +48°C.  It  is  recommended  to  observe  these  temperatures  during 
transport by container.
10.7.8 - Control configuration with the desuperheater
option
This configuration allows the user to enter a setpoint that is relative 
to  the  minimum  condensing  temperature  (default  =  30°C)  to 
increase the heating capacity reclaimed at the  desuperheaters, 
if  required.  The  percentage  of  the  reclaimed  heating  capacity 
compared with the total capacity rejected by the air heat exchanger 
increases in proportion to the saturated condensing temperature. 
For the control of the setpoint of the minimum saturated condensing 
temperature please refer to the Pro-Dialog control manual for the 
30RQM/30RQP units.
Other parameters directly affecting the effective capacity reclaimed 
at the desuperheater are principally: 
- The  unit  load  rates,  that  decide  whether  the  unit
operates at full load (100%) or part load (depending on the 
number of compressors per unit circuit).
- The  water  entering  temperature  in  the  desuperheater  and 
depending on the unit heating or cooling opera-ting mode:
• In heating mode the water heat exchanger entering water 
temperature
• In  cooling  mode  the  air  heat  exchanger  entering  air 
temperature.
Minimum Maximum
°C
6.8
(1)
°C
5
°C
-
(2)
°C
25
°C
30
°C
3
°C
0
(3)
Pa
0
Minimum Maximum
°C
8
°C
20
°C
3
°C
25
(2)
°C
30
°C
3
°C
-10
Pa
0
30
(1)
15
60
60
80
60
46
0
45
50
60
60
80
60
35
0
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents