8 - NOMINAL SYSTEM WATER FLOW CONTROL
8.5 - Units with hydraulic module and variable
speed pump – Setting a fixed flow for the system
The flow will be set to a nominal value. This value shall remain 
constant,  and  will  not  be  dependent  on  variations  in  the 
installation's load.
Contact  Carrier  Service  to  discuss  the  implementation  of  the 
procedures set out below.
8.5.1 - Cleaning procedure for the water circuit
Refer  to  the  cleaning  procedure  for  the  water  circuit  in  section 
8.3.1.
8.5.2 - Procedure for controlling the flow
Once the circuit is cleaned, set the required water flow by adjusting 
the pump frequency on the user interface. 
Stop the forced operation of the pump and configure the unit for 
the required control mode. 
Modify the control parameters:
- Water flow control method (fixed speed).
- Constant frequency value. 
By default, the unit is configured at the minimum speed (frequency: 
30 Hz).