Water Flow Detection; Frost Protection - United Technologies Carrier 30RQM 160 Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pump
Table of Contents

Advertisement

7 - WATER CONNECTIONS

7.3 - Water flow detection

7.3.1 - Standard unit
All units are equipped with a factory-set flow switch. It cannot be 
adjusted on site.
A water pump operating interlock must be wired to the unit if no 
hydraulic module is fitted. Terminals 34 and 35 are provided for 
connection of the water pump interlock (to be wired on site).
7.3.2 - Unit with hydraulic module (options 116)
The ''water flow detection'' functionality is handled by the option 
(via pressure sensors).

7.4 - Frost protection

CAUTION: Damage caused by frost is not covered by the
warranty.
The  plate  heat  exchanger,  the  pipes  and  the  hydraulic  module 
pumps can be damaged by frost. The components of the unit (heat 
exchanger, pipes, hydraulic module) will be protected by following 
the recommendations below. Protection of the remainder of the 
system is the responsibility of the installer. 
7.4.1 - Standard unit
If the chiller or the water pipes are in an area where the ambient 
temperature can drop below 0°C, it is recommended that one of 
the three following strategies is applied to protect the unit and the 
water  pipes  down  to  a  temperature  10  K  below  the  lowest 
temperature likely to occur locally:
1.  Add an anti-freeze solution (45% maximum);
2.  Drain the hydraulic circuits exposed to negative temperatures;
3.  Solution  with  heaters:  Order  (factory-installed)  option  41 
(electric heaters on the water heat exchanger and exchanger 
water outlet pipes) in order to protect the exchanger down to 
-20°C. If option 266 (water heat exchanger connection sleeves) 
is  also  ordered,  it  is  necessary  to  install  a  heater  on  each 
extension in order to protect the water pipes down to outdoor 
temperatures of -20°C. The anti-freeze and heater solutions 
can be combined.
7.4.2 - Unit with hydraulic module
The recommendations from the previous chapter (points 1 and 2) 
are applicable to the machines with hydraulic module and protect 
them against frost.
For the solution with heaters, order (factory-installed) option 42A 
(electric  heaters  on  the  water  heat  exchanger  and  various 
components of the hydraulic module including the expansion tank) 
to ensure protection of the entire unit down to -20°C. The anti-
freeze and heater solutions can be combined.
Frost protection of units with hydraulic modules require that water 
be circulated in the hydraulic circuit. The pump will periodically 
start automatically.
Combination  of  options  for  the  periods  when  the  machine  is  in 
standby mode.
Ambient unit
temperature range
without option 116
> 0°C to 48°C
-20°C to 0°C
Appropriate anti-freeze 
solution (for example 
(1)   Allow the pumps to circulate. If there is a valve, install a bypass (see diagram 
for winter position).
If  the  system  is  isolated  by  a  valve,  it  is  imperative  to  install  a 
bypass as indicated below.
Winter position
Unit
IMPORTANT REMINDERS: Depending on the atmospheric
conditions in your region, you need to:
- Add an appropriate anti-freeze solution to protect the
system down to a temperature of 10 K below the lowest
temperature likely to occur locally.
- For extended shut-downs, drain and add an anti-freeze
solution to the heat exchanger (use the drain valve
located at the water inlet).
- To prevent corrosion due to differential aeration, if the
system is to be empty for more than 1 month, the heat
transfer fluid circuit should be protected with a blanket
of dry, inert gas. (0.5 bar maximum). If the heat transfer
fluid does not meet Carrier's recommendations, a
nitrogen blanket must be applied immediately.
- In case of prolonged non-usage, the hydraulic circuits
must be protected by circulating a passivating solution.
(Consult a specialist).
- At the commencement of the next season, fill the system
with water treated with appropriate corrosion inhibitors.
- If auxiliary equipment is installed in the system, the
installer must ensure that the resultant flow rates are
still within the minimum and maximum values indicated
in the operating limits table (application data).
- If frost protection is dependent on electric heaters, never
deenergize the unit when frost protection is required. To
ensure protection, the main unit disconnect switch,
auxiliary heater circuit and the control circuit must be
energized (see wiring diagram to locate these
components). If it is not to be used in freezing conditions,
or during a prolonged power failure (planned or
unplanned), the water heat exchanger and external pipes
must be drained without delay. Damage caused by frost
is not covered by the warranty.
- The heat exchanger temperature sensors are part of its
frost protection: If piping trace heaters are used, ensure
the external heaters do not affect the measurements
provided by these sensors.
30RQM/30RQP 160-520
with option 116
-
-
Option 41
Option 42A
or
or
Appropriate anti-freeze 
solution (for example 
glycol)
glycol)
Closed
Water system
Open
Closed
(1)
(1)
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents