9 - MAIN COMPONENTS OF THE UNIT AND OPERATING CHARACTERISTICS
9.13 - Low temperature and brine solution
option (Option 6B)
Brine solution production from 0°C to -8°C is only possible with 
the low-temperature brine solution option (6B).
The  unit  is  equipped  with  insulation  on  the  suction  tubes.  The 
insulation  is  reinforced  on  the  low-temperature  brine  solution 
option.
The operating range depends on:
- the unit size,
- the glycol type,
- its concentration,
- the flow rate,
- the temperature of the glycol solution,
- the condensing pressure (ambient temperature).
9.13.1 - Frost protection
The low-pressure and frost protection thresholds of the evaporator 
depend on the antifreeze level in the water loop.
The evaporator pinch (LWT – SST) and the antifreeze protection 
threshold depend on this level.
It is therefore essential, when first activating the unit, to check the 
antifreeze level in the loop (circulate for 30 minutes to ensure good 
mixing homogeneity before sampling).
Refer to the manufacturer or supplier data to define the freezing 
temperature according to the measured concentration level. 
The minimum frost protection temperature must be entered in the 
unit controller's parameters.
This value will be used to configure the following protection:
1. Evaporator antifreeze protection.
2. Low-pressure protection.
For information, for the different antifreezes used in our laboratory, 
the protection values given by our supplier are as follows (these 
values may change depending on the suppliers).
It is therefore recommended that a medium or low temperature 
installation be commissioned by the manufacturer.
9.13.2 - Required glycol concentration
Ethylene and Propylene glycol freezing curve
Minimum frost protection temperature (°C)
Ethylene glycol (%)
Propylene glycol (%)
Minimum frost protection temperature based on the
leaving water temperature (example)
Leaving water temperature (°C)
For example, based on the above curves, if the ethylene glycol 
mass  concentration  measured  in  the  loop  is  30%,  the  frost 
protection temperature value of -14.8°C must be entered in the 
software.  This  corresponds  to  a  minimum  leaving  water 
temperature of -6.7°C. The control point must be adjusted as a 
result.
IMPORTANT:
- It is vital to perform a (minimum) annual inspection of
the glycol level and adjust the software's frost protection
based on the measured level.
- This procedure must be systematic when topping up
with water or antifreeze solution.
- Observe the minimum frost protection temperature
based on the leaving water temperature.
NOTE:
- In the case of frost protection of the unit by low air
temperature, the percentage of glycol must be evaluated
accordingly.
- The maximum glycol level in the case of units equipped
with a hydraulic module is 45%.
- In order to facilitate maintenance operations, it is
recommended to install isolation valves upstream and
downstream of the machine
43