Installation Of Multiple Heat Pumps; Distance To The Wall - United Technologies Carrier 30RQM 160 Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pump
Table of Contents

Advertisement

3 - DIMENSIONS AND CLEARANCES
WITH WATER BUFFER TANK MODULE
Legend
All dimensions are given in mm.
B
Clearances required for maintenance and air flow
C
Clearance recommended for coil removal
Water inlet
Water outlet
Air outlet, do not obstruct
Control box

3.4 - Installation of multiple heat pumps

It is recommended to install multiple heat pumps in a single row, 
arranged as shown in the example below, to avoid recycling of air 
from one unit to another.
If the floor space does not allow this arrangement, contact your 
Carrier distributor to assess the various installation options.
Main hydraulic connection
NOTE:
Non-contractual drawings.
When designing a system, refer to the certified dimensional
drawings provided with the unit or available on request.
Please refer to the certified dimensional drawings for the
positioning of the fixing points, weight distribution points
and centre of gravity coordinates.

3.5 - Distance to the wall

To guarantee correct operation in most cases:
If h < H, S minimum = 3 m
If h > H or S < 3 m, contact your Carrier distributor to assess the 
various installation options.
Anti-vibration
mounts
Electrical power connection
15