Electrical Data 30Rqm 160-520; Electrical Data 30Rqp 160-520 - United Technologies Carrier 30RQM 160 Installation, Operation And Maintenance Instructions

Reversible air-to-water heat pump
Table of Contents

Advertisement

4 - PHYSICAL AND ELECTRICAL DATA FOR 30RQM AND 30RQP UNITS

4.3 - Electrical data 30RQM 160-520

30RQM
Power circuit
Nominal voltage
Voltage range
Control circuit supply
Nominal unit current draw
(1)
Circuit A&B
Maximum unit input power
(2)
Circuit A&B
Cosine Phi unit at maximum power
Maximum unit current draw (Un-10%)
Circuit A&B
Maximum unit current draw (Un)
Circuit A&B -  Standard Unit
Circuit A&B - Unit with option 231
Maximum start-up current, standard unit (Un)
Circuit A&B
Max. start-up current, unit with soft starter (Un)
Circuit A&B
(1)  Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2)  Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage 
of 400 V (data given on the unit nameplate).
(3)  Maximum unit operating current at maximum unit power input and at 360 V.
(4)  Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate). 
(5)  Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of 
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8 
A; Start-up current 20 A; Power input: 1.75 kW.

4.4 - Electrical data 30RQP 160-520

30RQP
Power circuit
Nominal voltage
Voltage range
Control circuit supply
Nominal unit current draw
(1)
Circuit A&B
Cosine Phi unit at maximum power
Circuit A&B
Cosinus Phi unité à puissance maximale
Maximum unit current draw (Un-10%)
Circuit A&B
Maximum unit current draw (Un)
Circuit A&B -  Standard Unit
Circuit A&B - Unit with option 231
Maximum start-up current, standard unit (Un)
Circuit A&B
Max. start-up current, unit with soft starter (Un)
Circuit A&B
(1)  Conditions equivalent to the standardised Eurovent conditions (evaporator water input-output temperature = 12 °C/7 °C, outside air temperature = 35 °C).
(2)  Power input, compressors and fans, at the unit operating limits (saturated suction temperature 15 °C, saturated condensing temperature 68.3 °C) and nominal voltage 
of 400 V (data given on the unit nameplate).
(3)  Maximum unit operating current at maximum unit power input and at 360 V.
(4)  Maximum unit operating current at maximum unit power input and at 400 V (values given on the unit nameplate). 
(5)  Maximum instantaneous starting current at operating limits (maximum operating current of the smallest compressor(s) + current of the fan(s) + locked rotor current of 
the largest compressor).
Fan motor electrical data reported upstream of the variable drive at Eurovent equivalent conditions and motor ambient air temperature of 50 °C at 400 V: Current 3.8 
A; Start-up current 20 A; Power input: 1.75 kW.
18
160
V-ph-Hz
V
A
100
kW
80
0,88
(2)
(3)
A
144
(4)
A
133
A
100
(5)
A
307
(5)
A
261
160
V-ph-Hz
V
A
97
(2)
kW
81
0,88
(2)
(3)
A
142
(4)
A
131
A
98
(5)
A
305
(5)
A
259
180
210
230
240
270
400 - 3 - 50
360 - 440 
24 V via internal transformer
110
133
147
151
166
88
107
118
120
134
0,87
0,88
0,88
0,87
0,88
158
192
211
215
241
146
177
195
199
222
110
133
148
151
166
356
352
406
409
396
283
305
332
336
350
180
210
230
240
270
400 - 3 - 50
360 - 440 
24 V via internal transformer
107
130
144
147
162
88
108
118
120
134
0,88
0,88
0,88
0,88
0,88
154
189
208
211
237
142
174
192
195
218
108
131
146
148
164
353
349
402
405
392
279
302
329
332
346
310
330
380
430
470
191
199
233
266
294
152
161
188
215
236
0,87
0,88
0,88
0,88
0,88
273
289
337
385
422
252
266
310
354
390
192
200
233
266
296
462
440
485
529
600
389
394
438
482
527
310
330
380
430
470
186
195
227
260
288
153
161
188
215
237
0,88
0,88
0,88
0,88
0,88
268
284
331
378
416
247
261
305
348
383
188
197
230
262
291
458
436
479
523
594
384
389
433
476
520
520
322
258
0,88
460
425
326
636
562
520
316
259
0,88
454
419
321
629
556