Procedures For Single Megaflex 1000 To 1600; Initial Start-Up Of The Megaflex 1000 To 1600 - ABB MegaFlex UL S1 Series User Manual

Table of Contents

Advertisement

53/86

7.1 Procedures for single MegaFlex 1000 to 1600

7.1.1 Initial start-up of the MegaFlex 1000 to 1600

Warning!
Before proceeding to turn ON the UPS system, ensure that the AC and DC external isolators are OFF
and prevent their inadverted operation.
Ensure that the Output Load distribution can be powered and all the Output Isolators are open.
This procedure must be performed for the first start-up following the installation, with the UPS completely
switched Off and not powered.
Open the front door and make sure that:
All the connections to the input/output terminals or bus bars of the UPS have been made correctly.
The safety screens are fixed in their position.
The "Q1 – External UPS Output Circuit Breaker" and the "External Battery Breaker" must be open (Pos. O).
Q1 External UPS Output Circuit Breaker
with dedicated Auxiliary Contact to be
connected to the UPS is required.
See Section 4.11.2 of the Installation Guide.
LED ALARM
Command
Inverter ON
Command
System shutdown
1.
Switch-ON the Utility voltage from the input distribution (both Rectifier and Bypass if separated).
The UPS performs a "Self-test".
A successful termination of the tests will be indicated with Overall test
results "OK".
Commissioning cannot be continued should one or more tests result to be
negative. Please contact in this case your ABB Service Center.
At this stage the Electronic Power Supply and Control Panel are switched
ON and the Buzzer sounds.
Press "MUTE" key to reset Acoustical Alarm.
LED ALARM remains lit.
Megaflex UL
Q1
Load
MegaFlex 1000 to 1600
LEDs on Synoptic Diagram
LED 1
Rectifier
LED 2
Inverter
LED 3
Booster / Battery charger
LED LOAD PROTECTED
Command
Inverter OFF
Command
System shutdown RESET
UPS User Manual / REV-A
LED 4 Automatic Bypass
LED 5 LOAD on UPS
Continue →

Advertisement

Table of Contents
loading

Table of Contents