3Rd Level Programming - BFT CSB Xtreme (1.2) Installation And Operation Manual

Table of Contents

Advertisement

Par
Function

UPS

Exiting the menu/saving
Description of level 2 parameters

·
: Request for maintenance
: the request for maintenance is not active.
: at the end of the countdown, by means of counters  and , one of the programmed outputs is activated (see parameter
,,,)
: at the end of the countdown, by means of counters  and , one of the programmed outputs is activated (see parameter
,,,) and the bar lights fl ash twice.


and
·
: Programming maintenance cycles in thousands and millions
Thanks to the combination of the two parameters the countdown can be set after which a request for maintenance is signalled.
Thousands can be set with the  parameter, millions with the  parameter.
Example: to set 275 000 maintenance manoeuvres set  on 0.2 and  on 75.
The value displayed in the parameters updates along with the manoeuvres.

·
: TERMON (integrated motor heater system).
: system is always ON. Must be used only with maximum ambient temperature less than +10°C
WARNING: ambient temperatures >10°C may cause overheating and damages to the motor, not covered by warranty
: system is actived depending on motor temperature, measured by a NTC sensor (option). In case of NTC failure, system reverts to
setup 

·
: UPS
UPS TYPE
Square-wave or quasi-sine wave UPS
Pure-sinusoidal wave UPS with mains failure output
Pure-sinusoidal wave UPS without mains failure output
· Arm locking device confi guration:
To use the arm locking device, connect the enabling contact to OUT2 or OUT3 or OUT4 or OUT5 and set the corresponding
parameter ,,  or  to . Set advance electric lock disengagement ( -3nd level)
The following table gives the 3rd level functions and the single parameters.
= DEFAULT value set in factory.
Par
Function

Advanced setup

PDM dynamic input polarity

Output 2 polarity

Output 3 polarity

Output 4 polarity
Output 5 polarity

Advance electric lock disenga-

gement

Opening speed (%)
Control unit
Settable data
: disabled
: enabled, opens automatically during mains failure
: enabled, closes automatically during mains failure
ATTENTION:THIS SELECTION MAY BE DANGEROUS
Exit programming and view machine Status (see notes  automation Status
display after the 1st level table)
Internal detector, UPS input not connected
Connect mains failure output to UPS input
Use 230Vac relais, bobbin connected to mains supply, close contacts to UPS input
3ND
8.4
LEVEL PROGRAMMING
: no advanced setup
: N/A
: controlled entry and automatic exit
: input N.O.
: input N.C.
: N.O.
: N.C.
: 0,5s - : 1s - : 1,5s - : 2s - : 2,5s - : 3s
 - (MAXIMA ULTRA 68, ATM 90°, ATM 180°)
 - (MAXIMA ULTRA 35, Carbon)
- 25 -
= parameter value set during installation: must be indicated if
DEFAULT value is modifi ed.
Settable data