Time Setting; Enable/Disable Functions; Enable/Disable By Zone; Enable/Disable Individual Detection Devices (Inputs) - Bosch Radionics D8024 Operator's Manual

Analog fire alarm control panel
Hide thumbs Also See for Radionics D8024:
Table of Contents

Advertisement

4.4.2

Time Setting

Select the third option from the Main Menu, 3) Time, to change the time displayed on the D8024.
4.4.3

Enable/Disable Functions

Main Menu option four, 4) Enable, opens the Enable Menu. Main Menu option five, 5) Disable, opens the Disable Menu.
The content of the Enable and Disable menus is identical, allowing the operator to enable or disable zones, individual
devices (input), panel keys, day modes and outputs (relays).
Note:
NAC devices such as bells, horns and strobes cannot be enabled or disabled from Control Level 2.

4.4.3.1 Enable/Disable by Zone

To enable or disable input signals from devices by zone, select 1) Zone from the Enable or Disable Menu.
The display will prompt for the zone number. Key in the zone number and press the [Enter] key.
The display will repeat the zone number and ask "OK?". Press the [Yes] key to confirm. The panel will then enable or
disable all the input devices in the selected zone.
Note:
Any disabled circuit-driven device or relay on a circuit will still operate on output as programmed. Only the input signal
will be disabled. However, manual pull stations (alarm boxes) within the zone are not disabled.
When a device is disabled, the amber Point Bypassed LED on the LED display will light. The amber Trouble LED in the
corresponding zone of the ZONE/AREA display will also light, and the panel will display a disable message on the
alphanumeric display.

4.4.3.2 Enable/Disable Individual Detection Devices (Inputs)

To enable or disable input signals from individual detection devices, select 2) Input from the Enable/Disable Menu.
The display will prompt for the polling circuit (loop) number (1 or 2). Key in the circuit number and press [Enter].
The display will then prompt for the address of the device. Key in the address and press [Enter].
The display will then repeat the circuit number and address. Press the [Yes] key.
Note:
Any disabled circuit-driven device or relay on a circuit will still operate on output as programmed. Only the input signal
will be disabled.

4.4.3.3 Enable/Disable Panel Keys

To enable panel keys, press any of the control keys except the [No] key, or press the [>] key.
The panel will prompt "Do you want to enable the control keys?". Press the [Yes] key.
The panel then prompts for the Control Level 2 passcode. Key in the appropriate passcode.
The panel keys will be enabled for the programmed period of time. The display reverts to the Main Menu (see Figure 16).
After one minute, the display reverts to the normal display. Pressing the [System Reset] key will also return the display
to the normal display.
To disable the panel keys, select the third option, 3) Keys, from the Disable Menu. The display indicates that the panel
keys are inhibited and then returns to the normal display. Disabling the panel keys returns the D8024 to Control Level 1.
Copyright © 2001 Radionics
ENABLE:
1) Zone
4) Day Mode
DISABLE:
1) Zone
4) Day Mode

Figure 15: Enable/Disable Menus

[ACTIVE]
1) Commission 2) Test 3) Time
4) Enable 5) Disable 6) Print 7) View

Figure 16: Main Menu

D8024 Operator's Guide
Page 17
National Security Systems (800)457-1999
http://www.nationalsecuritysystems.com
2) Input
3) Keys
5) Outputs
2) Input
3) Keys
5) Outputs
[1]
D8024
Control Level 2
35394D