Mitsubishi FDT100VNXWVH Service Manual page 63

Hyper inverter packaged air-conditioners
Table of Contents

Advertisement

●DIP switch setting list
Switch
SW2
Address No. setting at plural indoor units control by 1 R/C
SW5-1
Master/Slave setting
SW5-2
SW6-1
SW6-2
Model selection
SW6-3
SW6-4
Test run, drain pump motor
SW7-1
SW7-2
Reserved
Reserved
SW7-3
Reserved
SW7-4
SW8-1
Anti-freeze control
Reserved
SW8-2
SW8-3
Reserved
Reserved
SW8-4
JSL1
Superlink terminal spare
Note(1) : SW8 : FDE only
Table 1: Indoor unit model selection with SW6-1-SW6-4
Switch
SW6-1
SW6-2
SW6-3
SW6-4
Table 2: Indoor unit Master/Slave setting with SW5-1,SW5-2
Switch
Master
Slave1
Slave2
Slave3
Description
Master * /Slave
Normal * /Test run
Valid/Invalid *
Normal * /switch to spare
* Default setting
50VH
60VH
71VH
100VH 125VH
ON
ON
ON
ON
OFF
ON
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
SW5-1 SW5-2
OFF
OFF
ON
OFF
ON
OFF
ON
ON
62
-
Default setting
0
OFF
OFF
As per model
Normal
OFF
OFF
OFF
OFF
OFF
OFF
Invalid
OFF
OFF
OFF
With
140VH
OFF
ON
OFF
OFF
ON
ON
ON
ON
-
'20 • PAC-SM-351
Remark
0-F
See table 2.
See table 1.
Keep OFF
Keep OFF
Keep OFF
Keep OFF
Keep OFF
Keep OFF