E16 Indoor Fan Motor Anomaly - Mitsubishi FDT100VNXWVH Service Manual

Hyper inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E16
Remote control:
1. Applicable model
2. Error detection method
Detected by rotation speed of
indoor fan motor
3. Condition of error displayed
• When actual rotation speed of
indoor fan motor drops to lower
-1
than 200min
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
• After 2-seconds, it starts
again automatically, but if this
error occurs 4 times within
60 minutes after the initial
detection.
4. Presumable cause
• Defective indoor unit control
PCB
• Foreign material at rotational
area of fan propeller
• Defective fan motor
• Dust on indoor unit control
PCB
• Blown fuse
• External noise, surge
Note:
LED
Green
Red
Keeps flashing 1-time flash
Indoor
Keeps flashing Stays OFF
Outdoor
5. Troubleshooting
Diagnosis
Does any
foreign material
intervene in rotational area
of fan propeller?
NO
Does the fan
rotate smoothly when turned
by hand?
YES
Is DC280V
detected between Œ- of
fan motor connector
CNM?
YES
Is the fuse F1 ot F2 blown?
Power source reset
Is it normalized?
105
-
Content
Indoor fan motor anomaly
YES
NO
Note (1)  for GND
(1)
NO
NO
YES
NO
YES
-
'20 • PAC-SM-351
Countermeasure
Remove foreign material.
Replace the fan motor.
Check power voltage.
Replace faulty fan motor
and indoor unit control PCB.
Replace fan motor. (If the
error persists after replacing
the fan motor, replace the
indoor unit control PCB.)
Malfunction by temporary
noise