Mitsubishi FDT100VNXWVH Service Manual page 153

Hyper inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E28
Remote control:
1. Applicable model
All models
2. Error detection method
Detection of anomalously low
temperature (resistance) of
remote control temperature
sensor (Thc)
3. Condition of error displayed
When the temperature sensor
detects -50°C or lower for
5 seconds continuously,
the compressor stops. After
3-minute delay, the compressor
starts again automatically, but
if this error occurs again within
60 minutes after the initial
detection.
4. Presumable cause
• Faulty connection of remote
control temperature sensor
• Defective remote control
temperature sensor
• Defective remote control PCB
Note:
After 10 seconds has passed since remote control temperature sensor was switched from invalid to valid, E28 will not be displayed even if the
temperature sensor harness is disconnected. At same time the temperature sensor, which is effective, is switched from remote control temperature sensor
to indoor return air temperature sensor. Even though the remote control temperature sensor is set to be effective, the return air temperature displayed
on remote control for checking still shows the value detected by indoor return air temperature sensor, not by remote control temperature sensor.
RUN light TIMER light
Indoor
display
Green LED Red LED
Outdoor unit
control PCB
Keeps flashing Stays OFF
5. Troubleshooting
Diagnosis
Is the remote
control temperature sensor
Is the remote
connected properly?
control temperature sensor
connected properly?
YES
YES
Are the
characteristics of
remote control temperature
sensor OK?
Are the
Is the temperature sensor
characteristics of
wire OK?
remote control temperature
sensor OK?
Is the temperature sensor
wire OK?
Temperature-resistance characteristics of remote control temperature sensor (Thc)
Temperature (°C)
Resistance value (kΩ)
0
65
1
62
2
59
4
53
6
48
Temperature-resistance characteristics of remote control temperature sensor (Thc)
8
44
Temperature (°C)
Resistance value (kΩ)
10
40
0
12
36
14
33
1
16
30
2
18
27
4
20
25
6
22
23
24
21
8
26
19
10
28
18
12
14
16
18
20
22
24
26
28
152
-
Content
Remote control
temperature sensor anomaly
NO
NO
NO
NO
YES
YES
Temperature (°C)
Resistance value (kΩ)
30
32
34
36
38
40
Temperature (°C)
42
65
30
44
46
62
32
48
59
34
50
53
36
52
48
38
54
56
44
40
58
40
42
60
36
44
33
46
30
48
27
50
25
52
23
54
21
56
19
58
18
60
-
'20 • PAC-SM-351
Countermeasure
Correct. ➞ Insert connector
securely.
Defective remote control
temperature sensor ➞
Replace.
Defective remote control
PCB ➞ Replace.
(Defective remote control
temperature sensor input
circuit)
16
15
14
13
12
11
Resistance value (kΩ)
9.9
16
9.2
8.5
15
7.8
14
7.3
13
6.7
12
6.3
5.8
11
5.4
9.9
5.0
9.2
8.5
7.8
7.3
6.7
6.3
5.8
5.4
5.0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents