Mitsubishi FDT100VNXWVH Service Manual page 104

Hyper inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
E11
Remote control:
1. Applicable model
2. Error detection method
IU address has been set using
the "Master IU address set"
function of remote control.
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake of address setting
method
(
Address setting from remote
control can't be done
Note:
LED
Green
Red
Keeps flashing Stays OFF
Indoor
Keeps flashing Stays OFF
Outdoor
5. Troubleshooting
E11 occurs
Is "Master IU
address set" function of remote
control used?
In case the wiring is below and "Mastar IU address
set" is used, E11 is appeared.
IU
R/C
)
Content
Address setting error of
Diagnosis
YES
IU
IU
103
-
-
'20 • PAC-SM-351
indoor units
Countermeasure
Change of address setting
method
Set the address by DIP
switch SW2 on indoor unit
control PCB.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents