Mitsubishi FDT100VNXWVH Service Manual page 129

Hyper inverter packaged air-conditioners
Table of Contents

Advertisement

Error code
Indoor control PCB
Remote control:
E59
Outdoor control PCB
Outdoor inverter
1. Applicable model
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
LED
Green
Keeps flashing
Keeps flashing
Yellow LED
PCB
Stays OFF
5. Troubleshooting
From previous page
power transistor
module OK?
After power OFF, turn SW10-4 of
inverter PCB ON and connect the
inverter checker. Then power ON
again.
inverter output OK?
(Check by inverter
checker.)
Try to restart several times.
Does it start?
Red
Content
Stays OFF
5-time flash
Compressor startup failure (2/2)
Diagnosis
YES
Is the
(Inverter PCB anomaly)
NO
YES
Is the
NO
Note(1) Several times restarting
may recover it, because
liquid refrigerant migrated
in the compressor could be
YES
discharged from the
compressor.
NO
128
-
-
'20 • PAC-SM-351
Countermeasure
Replace inverter PCB.
Replace inverter PCB.
Replace compressor.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents