Contents of operation
1)
Air capacity control
Item
ULo
Lo
Twin
type
Auto, Me
Hi
ULo
Lo
Triple
type
Auto, Me
Hi
Note (1) Ranges A and B are as shown below.
2)
When this control has continued for more than 30 minutes continuously,the following wind direction control is per-
formed.
a) When the vertical wind direction is set at other than the vertical swing,the flaps change to the horizontal po-
sition.
b) When the horizontal wind direction is set at other than the horizontal swing,the louver changes to the vertical
position.
(iii) Reset condition
Humidity is less than 55%.
(b) SRK-ZR series
(i)
Operating conditions
When the following conditions have been satisfied for more than 30 minutes after starting operation
1)
Compressor's command speed is 28 rps (SRK100: 20 rps) or higher.
2)
Detected value of humidity is 68% or higher.
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Upper limit of compressor's speed
Indoor fan
Range A
38
-
-
Model
SRK50, 60ZSX-W
RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 50 rps, RangeC: 30 rps
Adaptable to compressor speed
RangeA: 70 rps (SRK60: 80 rps), RangeB: 50 rps,
RangeC: 30 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
RangeA: 50 rps, RangeB: 50 rps, RangeC: 24 rps
Adaptable to compressor speed
RangeA: 50 rps, RangeB: 50 rps, RangeC: 30 rps
Adaptable to compressor speed
RangeA: 70 rps (SRK60: 80 rps), RangeB: 50 rps,
RangeC: 30 rps
Adaptable to compressor speed
Range C
Range B
60
68
73
Humidity(%)