Selecting The Power Cables; General Rules - ABB ACS800 Series Hardware Manual

Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

60

Selecting the power cables

General rules

Dimension the mains (input power) and motor cables according to local
regulations:
• The cable must be able to carry the drive load current. See chapter
data
• The cable must be rated for at least 70
temperature of conductor in continuous use. For US, see
requirements.
• The inductance and impedance of the PE conductor/cable (grounding wire) must
be rated according to permissible touch voltage appearing under fault conditions
(so that the fault point voltage will not rise excessively when a ground fault
occurs).
• 600 VAC cable is accepted for up to 500 VAC. 750 VAC cable is accepted for up
to 600 VAC. For 690 VAC rated equipment, the rated voltage between the
conductors of the cable should be at least 1 kV.
For drive frame size R5 and larger, or motors larger than 30 kW (40 hp), symmetrical
shielded motor cable must be used (figure below). A four-conductor system can be
used up to frame size R4 with up to 30 kW (40 hp) motors, but shielded symmetrical
motor cable is recommended.
WARNING! Do not use unshielded single-core supply cables in IT (ungrounded)
networks. A dangerous voltage can become present on the non-conductive outer
sheath of the cable. This can cause injury or death.
Note: When continuous conduit is employed, shielded cable is not required.
A four-conductor system is allowed for input cabling, but shielded symmetrical cable
is recommended. To operate as a protective conductor, the shield conductivity must
be as follows when the protective conductor is made of the same metal as the phase
conductors:
Cross-sectional area of the phase
conductors
Compared to a four-conductor system, the use of symmetrical shielded cable
reduces electromagnetic emission of the whole drive system as well as motor
bearing currents and wear.
The motor cable and its PE pigtail (twisted shield) should be kept as short as
possible in order to reduce electromagnetic emission.
Planning the electrical installation
for the rated currents.
2
S (mm
)
S < 16
16 < S < 35
35 < S
°
°
C (158
F) maximum permissible
Minimum cross-sectional area of the
corresponding protective conductor
2
S
(mm
)
p
S
16
S/2
Technical
Additional US

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents